Field Settings from Outdoor Unit
SiUS331708EA
121
Field Settings and Test Operation
2.5
Monitor Mode
The numbers in the No. column represent the number of times to press the
SET
(BS2)
button.
Note: Various
Settings
No.
Setting item
LED display
Data display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0
Various setting
l h h h h h h
See the note below.
1
Cool / heat unified address
l h h h h h k
Lower 6 digits
2
Low noise / demand address
l h h h h k h
3
Not used
l h h h h k k
4
AIRNET address
l h h h k h h
5
Number of connected indoor units
l h h h k h k
7
Number of connected zone units
(excluding outdoor and BS unit)
l h h h k k k
8
Number of outdoor units
l h h k h h h
11
Number of zone units (excluding
outdoor and BS unit)
l h h k h k k
Lower 6 digits
12
Number of terminal blocks
l h h k k h h
Lower 4 digits:
upper
13
Number of terminal blocks
l h h k k h k
Lower 4 digits: lower
14
Error description (the latest)
l h h k k k h
Error code table
Refer to page
152.
15
Error description
(1 cycle before)
l h h k k k k
16
Error description
(2 cycle before)
l h k h h h h
20
Contents of retry (the latest)
l h k h k h h
21
Contents of retry (1 cycle before)
l h k h k h k
22
Contents of retry (2 cycle before)
l h k h k k h
25
Normal judgment of outdoor units
PCB
l h k k h h k
Lower 2 digits:
k h
Abnormal
h k
Normal
h h
Unjudgment
Selection of check item
Confirmation on check item
Press the
MODE (BS1)
button and
enter the monitor mode.
Press the
SET (BS2)
button and
select a check item according to the
LED pattern.
Press the
RETURN (BS3)
button to
display different data of check item.
Press the
RETURN (BS3)
button
and return to the initial status of
monitor mode.
∗
If you become unsure of how to
proceed, press the
MODE (BS1)
button and return to the setting
mode 1.
H1P H2P H3P H4P H5P H6P H7P
Emergency operation /
backup operation setting
ON
l
h
h
k
h
h
h
OFF
l
h
h
h
h
h
h
Defrost select setting
Short
l
h
h
h
k
h
h
Medium
l
h
h
h
l
h
h
Long
l
h
h
h
h
h
h
Te setting
H
l
h
h
h
h
k
h
M
l
h
h
h
h
l
h
L
l
h
h
h
h
h
h
Tc setting
H
l
h
h
h
h
h
k
M
l
h
h
h
h
h
l
L
l
h
h
h
h
h
h
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...