FWD

Ducted fan units

4PW17549-3

Installation and operation manual

d

imensions

• 

Intake module with flat filter class EU 2 (See figure 2)

• 

Standard unit (See figure 5)

The dimensions mentioned on the left side are related to left-hand 
hydraulic attachments and the dimensions mentioned on the right 
side are related to right-hand hydraulic attachments.

1

 

6 fast-coupling slots

2

 

Condensate discharge - horizontal installation

3

 

Condensate discharge - vertical installation

4

 

Hydraulic connections

4 = standard heat exchanger

4 DF = additional heat exchanger

5

 

Air delivery

6

 

Air intake

6A = supply terms

6B = changeable during installation

7

 

Round pre-sheared element (Ø100 mm) for fresh air intake

i

nstallation

The FWD air conditioning and hot-air heating units may be installed 
either in horizontal or vertical position. Check that the desired instal-

lation complies with one of the pictures shown in figure 3 in which 
both possible configurations (AA or AB) are suitable to work for hea

-

ting and cooling.

In normal operation, particularly with the fan at minimum speed and ambientair 
with high relative humidity, condensation may form on the air outlet and on 
some external parts of the unit. To avoid such issues while always remaining 
within the operating limits envisaged for the unit, it is necessary to limit the 
(average) temperature of the water inside the heat exchanger. In particular, the 
difference between the air dew point (TA,DP) and the average water 
temperature(TWM) must NOT exceed 14 °C, according to the following 
relationship:

TW>TA,DP-14 °C

Example: in the case of ambient air at 25 °C with 75 % relative humidity, the dew 
point value is about 20 °C and, therefore, the average temperature of the water in 
the coil must be greater than 20 - 14 = 6 °C in order to avoid condensation 
issues. In the event the indoor unit is stopped for a prolonged period, with the 
fan stopped and circulation of cold water in the heat exchanger, condensation 
may also form on the unit’s exterior. In this case it is advisable to install the 
3-way (or 2-way) valve accessory in order to stop the flow of water in the coil 
when the fan is stopped.

Horizontal or vertical installation

(See figure 3)

AA

Inlet and outlet of air are in a straight line

AB

Inlet of air is not in a straight line with the outlet of air

Configuration of the unit

The units are always supplied in AA configuration, but the air inlet posi

-

tion may be changed during the installation.

Description of the kit (See figure 6)

1

 

Upper closing panel

2

 

Lower closing panel

3

 

Pre-sheared element for external air inlet

4

 

Centrifugal fans

5

 

Standard heat exchanger

6

 

Additional heat exchanger (DF)

7

 

Condensate tank for wall mounting (tube Ø3/8”)

8

 

Condensate tank for ceiling mounting (tube Ø3/8”)

9

 

Heat exchanger hydraulic attachments

10

 

Condensate discharge attachments

11

 

Terminal strip

12

 

Load-bearing structure

It is advisable to install any accessories on the standard equipment be-
fore positioning it, referring to the technical sheets.

The sections of the inlet and delivery pipes are rectangular and drilled with 

holes for fixing the available accessories. A round pre-sheared element 

(Ø100 mm) is present on both side panels of the unit for the direct inlet of 

fresh air.

If the installation differs from the supply terms, the layout must be chan-

ged by dismantling the unit as shown in figure 6.

It is possible to orient the exchanger’s attachments on the opposite side 
as follows:

remove the upper and lower closing panels (1+2),

remove the condensate tank for the horizontal installation (8)

loosen the 4 fixing screws of the motor support, without unscrewing them all 

the way (7),

remove the heat exchanger (5) by unscrewing the 4 fastening screws, pull it 
out and turn it; eliminate the pre-sheared elements on the opposite side panel, 
re-insert the heat exchanger and tighten the screws,

reassemble the previously listed components,

stop the outlet holes of the previously used manifolds with anticondensing in-
sulating material.

Installing the unit

Fix the standard unit to the ceiling or wall using at least 4 of the 6 slots;

• 

For horizontal installation (ceiling mounting) 

it is advisable to use M8 

threaded bars, screw anchors suitable for the unit’s weight and to 
arrange for the positioning of the unit using 2 M8 bolts and a wa-
sher the diameter of which is suitable for inserting the slot and for 

then fixing the unit.

Before tightening the check nut, adjust the closing of the main nut 
so that the unit will slant correctly, i.e. for facilitating the discharging 

of the condensate (see figure 4).

The correct slant is achieved by tilting the inlet downwards as com-
pared to the outlet until a difference in level of about 10 mm is obtai-
ned from one end to the other. Make the hydraulic connections with 
the heat exchanger and, for cooling operations, with the condensa-
te discharge. Use one of the 2 drains of the auxiliary tank, visible on 

the outside of the unit’s side panels (see figure 5): horizontal (tank) 

and vertical condensate discharge.

• 

For vertical installations (wall mounting)

, fix the unit so that water flow 

out toward the condensate discharge used. A slant equivalent to a 
difference in level between the two side panels of about 5 mm is 
enough.

The two condensate discharge tubes of the main tank are located 
inside the side panels and may be accessed through a membrane 
type passage that should be perforated for passing the discharge 
tube through it.
It is advisable not to remove the aforesaid membrane type passage 
because it prevents the sharp edge of the hole on the side panel 
from damaging the condensate discharge tube over time.

• 

To connect the unit to the condensate discharge line

use a flexible rubber 

tube and fix it to the chosen discharge tube (Ø3/8”) by means of a me

-

tal  clamp  (use  the  discharge  that  is  located  on  the  hydraulic  at

-

tachments side).

To assist the draining of the condensate, slant the discharge tube 
downwards by at least 30 mm/m making sure that its entire route is 
clear and free from bends or blockages.

• 

Installation of air filter.

 For inlet, the filter module may be installed ei

-

ther in the same line as the outlet (configuration AA) or at 90° as 
compared to the unit (configuration AB). In the latter case the front 

lower closing panel must be moved by adjusting the 6 screws that 

fix it to the unit. The panel will then be installed at the bottom of the 

unit.

Both ends of the filtering module are drilled to match the holes on 

the intake inlet of the unit.
As such, it will be possible to couple the module to the unit and 
achieve, at the other end, a positioning of the holes that is identical 
to that of the intake inlet of the air handling unit.

The drilled holes at one end of the module are Ø5 mm; this is the 

part that is to be coupled directly to the unit.
At the other end the diameter of the holes is 3.5 mm to ensure that 

the screws, which will be used for fixing other parts (field supply) 

will be tight.

The overall dimensions are shown in figure 2.

2

Summary of Contents for FWD04ACTN6V3

Page 1: ...oren met kanaalaansluiting Nederlands Manual de instalaci n y operaci n Fan coils entubados Espa ol Manuale d installazione e d uso Unit fan coil canalizzata Italiano Manual de instala o e de funciona...

Page 2: ......

Page 3: ...2 274 53 29 241 98 579 506 382 510 17 273 53 294 757 17 17 C D 757 29 5 1 D 5 1 1 0 0 17 FWD04 FWD06 FWD08 10 D 646 856 1066 H 223 223 223 FWD12 FWD16 18 1066 1276 296 296 FWD04 10 FWD12 18 A FWD04 FW...

Page 4: ...FWEC1 FWD 04 12 FWEC1 FWD 16 18 EPIB6 UT66000880 UT66000881...

Page 5: ...FWEC2 3 FWD 04 12 FWEC2 3 FWD 16 18 UT66000888 UT66000889...

Page 6: ...FWECSA FWD...

Page 7: ...ning and intended for use in civil comfort applications do not install the unit in rooms where inflammable gases are pre sent do not let water spray directly on the unit install the unit on ceilings o...

Page 8: ...ttachments on the opposite side as follows 1 remove the upper and lower closing panels 1 2 2 remove the condensate tank for the horizontal installation 8 3 loosen the 4 fixing screws of the motor supp...

Page 9: ...ry accessory In order to make the electrical connections you must remove the lower closing panel see figure 6 to access the terminal strip The power cables power supply and control must be routed to t...

Page 10: ...ting If the unit does not work properly first check the points reported in the table below before requesting service If the problem cannot be solved contact your dealer or service centre Symptom 1 The...

Page 11: ...20 C 43 C Spannungstoleranz 10 Grenzwert relative Luftfeuchtigkeit der Raumluft RH 85 nicht kondensierend Auswahl des Installationsortes F r die Klimatisierung der Raumluft und f r den Einsatz f r Anw...

Page 12: ...bschnitte des Lufteinlass und der Auslassrohre sind rechteckig und mit Bohrl chern versehen zur Befestigung der vorhandenen Zubeh rteile Ein rundes vorgeschnittenes Element 100 mm ist auf beiden Seite...

Page 13: ...Verkabelung S mtliche bauseitigen Verdrahtungen und Bauteile m ssen von einem zugelassenen Elektriker installiert werden und den entsprechenden rtlichen und staatlichen Vorschriften entsprechen F hren...

Page 14: ...ng sowie Reini gung bedeutet Energieerhaltung und Kostenersparnis Vorschriften zur Entsorgung Die Demontage der Einheit muss gem den jeweiligen rtlichen und staatlichen Vorschriften erfolgen Fehlerbes...

Page 15: ...s condensation S lection d un emplacement Appareils con us pour la climatisation de l air ambiant et destin s trelis s pour des applications de confort civil ne pas installer l unit dans des locaux o...

Page 16: ...ngeur thermique 10 Fixations de l vacuation d eau de condensation 11 Barrette de raccordement 12 Structure de support de charge Nous vous recommandons d installer les accessoires sur l quipement stand...

Page 17: ...ons expos es directement aux rayons du soleil ou des positions soumises des courants d air chaud ou froid directs Ne placez pas d obstacles sur le chemin qui vous emp cheraient de lire correctement la...

Page 18: ...oyez l air comprim ou la vapeur basse pression sans endommager les ailettes de l changeur thermique Avant de le faire fonctionner en t v rifiez r guli rement l vacuation de l eau de condensation NOTE...

Page 19: ...ieve vochtigheidslimiet van de omgevingslucht RH 85 zonder condensvorming Keuze van de montageplaats installeer het toestel niet in een ruimte met ontvlambare gassen zorg ervoor dat er geen water rech...

Page 20: ...de technische fiches De inlaat en aanvoerleidingen zijn rechthoekig en voorzien van gaten voor de beschikbare accessoires Aan beide zijpanelen van de unit is een op voorhand nagesneden element 100 mm...

Page 21: ...lektricien moet instaan voor het uitvoeren van de lokale bedrading en monteren van de onderdelen Dit moet overeenkomstig de lokale en nationale voorschriften gebeuren Schakel het toestel uit voordat u...

Page 22: ...hadigen Controleer de condensaatafvoer regelmatig voordat u de unit in de zomer gebruikt NOTE Correct en regelmatig onderhoud en reinigen werkt energiebesparend en voorkomt dure reparaties Eisen bij h...

Page 23: ...nados a ser utilizados en aplicaciones de confort civil no instale la unidad en salas con presencia de gases inflamables impida las salpicaduras directas de agua en la unidad instale la unidad en tech...

Page 24: ...3 8 8 Dep sito de agua de condensaci n para montaje en el techo tubo de 3 8 9 Conexiones hidr ulicas del intercambiador de calor 10 Conexiones de descarga de agua de condensaci n 11 Regleta de conexi...

Page 25: ...acceso para realizar el ajuste de las funciones y para detectar la temperatura Procure evitar posiciones en las que el equipo est expuesto a los rayos directos del sol o posiciones en las que el equi...

Page 26: ...n evitando da ar las aletas del intercambiador de calor Antes de operar la unidad en verano compruebe peri dicamente las descargas de agua de condensaci n NOTE El mantenimiento y limpieza adecuada y...

Page 27: ...e Apparecchi progettati per la climatizzazione dell aria ambiente e destinati all utilizzo in applicazioni di comfort civile non installare l unit in ambienti in cui sono presenti gas infiammabili non...

Page 28: ...ambiatore di calore 10 Attacchi scarico condensa 11 Morsettiera 12 Struttura portante Si consiglia di installare tutti gli accessori sull unit standard prima di collocarla nella posizione stabilita fa...

Page 29: ...i soggette a correnti di caria calda o fredda diretta Non mettere alcun tipo di oggetto che ostacoli la corretta lettura della temperatura Collegamenti da effettuarsi in loco Sia i collegamenti elettr...

Page 30: ...pulire con aria compressa o con vapore a bassa pressione senza danneggiare le alette Prima di accenderlo d estate controllare che la condensa sia regolarmente scaricata NOTE Una manutenzione e una pul...

Page 31: ...FWD 4PW17549 3 Daikin Daikin Daikin n n 5 C 95 C n 10 bar n 20 C 43 C n 10 n RH 85 FWD 1 3 180 FWD 1 2 E M4 kit 1 FWD 1...

Page 32: ...2 2 5 1 6 2 3 4 4 4 DF 5 6 6A 6B 7 100 mm FWD 3 AA AB TA DP TWM 14 C TW TA DP 14 C 25 C 75 20 C 20 14 6 C 3 AA AB AA kit 6 1 2 3 4 5 6 DF 7 3 8 8 3 8 9 10 11 12 100 mm 6 1 1 2 2 8 3 7 4 5 4 5 6 4 6 M8...

Page 33: ...FWD 4PW17549 3 3 8 30 mm m AA 90 AB 6 5 mm 3 5 mm 2 9 FWD AA 10 FWD AB kit EDEH IL 3 mm F 6 7 FWD 3 WH 7 BK BU GY GNYE RD WH CN F IL M OFF 3...

Page 34: ...FWD 4PW17549 3 OFF OFF 6 8 8 1 2 1 STOP 0 ON I 2 3 4...

Page 35: ...Selec o do local Aparelhos projetados para a climatiza o do ar ambiente e destinados utiliza o em aplica es de conforto civil n o instale a unidade em salas que contenham gases inflam veis n o permit...

Page 36: ...de calor 10 Anexos para a descarga de condensado 11 Placa de bornes 12 Estrutura de suporte de carga Aconselha se que eventuais acess rios sejam instalados nos equipamento padr o antes de o colocar no...

Page 37: ...os solares bem como posi es sujeitas a correntes de ar quente ou frio N o coloque obst culos em redor do painel para que a medi o da temperatura seja a correcta Liga es el ctricas locais Toda a cablag...

Page 38: ...ifique regularmente as descargas de condensado NOTE A manuten o e limpeza adequadas regulares produzem poupan a de energia e custos menores Exig ncias relativas elimina o A desmontagem da unidade deve...

Page 39: ...FWD 4PW17549 3 Daikin Daikin Daikin 5 C 95 C 10 20 C 43 C 10 RH 85 FWD 1 3 180 FWD 1 EU 2 M4 1 FWD 1...

Page 40: ...2 EU 2 2 5 1 6 2 3 4 4 4 DF 5 6 6A 6B 7 100 FWD 3 AA AB TA DP TWM 14 C TW TA DP 14 C 25 C 75 20 C 20 14 6 C 3 2 3 AA AB AA 6 1 2 3 4 5 6 DF 7 3 8 8 3 8 9 10 11 12 100 6 1 1 2 2 8 3 7 4 5 4 5 6 4 6 M8...

Page 41: ...FWD 4PW17549 3 30 90 6 5 3 5 2 9 FWD AA 10 FWD A EDEH IL 3 F 6 7 FWD 3 WH 7 BK BU GY GNYE RD WH CN F IL M OFF 3...

Page 42: ...FWD 4PW17549 3 OFF OFF 6 8 8 1 2 NOTE Symptom 1 STOP 0 ON I Symptom 2 Symptom 3 4...

Page 43: ...ndensation Val av installationsplats Apparater konstruerade f r klimatkontroll av omgivande luft avsedd f r anv ndning i civila komfortapplikationer Installera inte aggregatet i omgivningar med brandf...

Page 44: ...erna In och utloppens r rdel r rektangul r och f rsedd med h l f r fasts ttning av de tillbeh r som finns tillg ngliga P b da sidorna av aggregatets paneler finns en f rskuren rund del 100 mm f r dire...

Page 45: ...ensst mmer med det nominella str mv rdet som anges p aggregatets m rkskylt Varje aggregat beh ver en brytare IL p str mf rs rjningen med ett avst nd p minst 3 mm mellan ppningskontakterna och en passa...

Page 46: ...ortskaffning Apparaten ska bortskaffas i enlighet med g llande lokal och nationell lagstiftning Fels kning Om aggregatet inte fungerar som det ska ska man f rst av allt kontrollera punkterna i tabelle...

Page 47: ...4PW17549 3 Zandvoordestraat 300 B 8400 Oostende Belgium...

Reviews: