The installation of the filter module is schematically shown in:

figure 9: installation of filter intake modules on FWD with 
configuration AA.

figure 10: installation of filter intake modules on FWD with 
configuration AB.

Use the self-tapping screws supplied with the kit.

A few rules to follow

Purge the air from the heat exchanger, with pumps stopped, 
by means of the air valves located adjacent to the attachments 
of the heat exchanger itself.

When implementing a duct type system, it is advisable to pla-

ce vibration damping joints (field supply) between the chan

-

nelling and the unit.

If you wish to install an electrical resistance module (EDEH) as 

accessory, the delivery vibration damping joint should be heat 
resistant.

The ducting, especially the delivery one, should be insulated 
with anticondensing material.

Provide an inspection panel adjacent to the equipment for the 
maintenance and cleaning operations.

Install the control panel on the wall. Choose a position that is 
easy to access for the setting of the functions and for detecting 
of the temperature. Try to avoid positions that are directly ex-
posed to sun rays, or positions subject to direct hot or cold air 
currents. Do not place obstacles in the way that would prevent 
the correct reading of the temperature.

f

ield

 

wiring

All  field  wiring  and  components  must  be  installed  by  a 

licensed electrician and must comply with relevant local and 
national regulations.

Carry out the electrical wiring after having turned the power off. For 
options, refer to the appropriate manual.

Check that the power supply corresponds to the nominal power supply 
stated on the unit nameplate.

Each unit requires a switch (IL) on the power supply with a distance of 

at least 3 mm between the opening contacts and a suitable safety fuse 

(F).

Power consumption is shown on the data plate fixed to the unit.

Make sure to carefully execute the wiring in function of the combina-
tion unit/controller and this according to the correct wiring diagram de-
livered with every accessory.

In order to make the electrical connections you must remove the lower 

closing panel (see figure 6) to access the terminal strip.

The power cables (power supply and control) must be routed to the 

terminal strip through the membrane passage that is on the side panel 
of the unit on the side opposite the hydraulic attachments.

Figure 7 shows the FWD wiring diagram without control panel.

The motors of the units run at 3 speeds.

The common wire of the motor is the white one (WH).

If the common wire is not connected correctly, the motor 
would be damaged irreparably.

Wiring parts table 

(See figure 7)

BK .......................... Black = maximum speed
BU or GY................ Blue or Gray = medium speed
GNYE .................... Green-Yellow = earth
RD ......................... Red = minimum speed
WH ......................... White = common wire

- - - - ....................... Field wiring
CN ......................... Connector
F ............................

Fuse (field supply)

IL............................

Line switch (field supply)

M ............................ Motor

¿

 ............................ Connections to controller

t

est

 

rUn

Check that the equipment has been installed so that it guarantees the 
required slant.

Check that the condensate discharge is not clogged (by rubble depo

-

sits, etc.).

Check the seal of the hydraulic connections.

Check that the electrical wiring is perfectly tight (perform this check 
with voltage OFF).

Be sure that the air purge of the heat exchanger has been carried out 
correctly.

Turn on the power supply and check the unit running.

U

se

To use the unit, refer to the instructions in the installation and operation 
manual of the controller. Dedicated controllers are available as acces-
sory.

m

aintenance

 

and

 

cleaning

For safety reasons before carrying out any maintenance or cleaning 
operation, turn off the unit and cut the voltage by turning the line switch 
to OFF.

Maintenance

The maintenance operations for the FWD air conditioner and hot-air 

heating units are limited to the periodic cleaning of the air filter and the 
heat exchanger, and the checking of the working efficiency of the con

-

densate discharge.

Only skilled personnel may perform the maintenance.

Pay utmost attention during the maintenance operations: accidentally 
coming into contact with some of the metallic parts might cause injuri-
es, therefore use safety work gloves.

Every time the units are started after a long idle period, make sure that 
air is NOT present in the heat exchanger.

The motor is maintenance-free since it is equipped with self-lubricating 
bearings.

3

Summary of Contents for FWD04ACTN6V3

Page 1: ...oren met kanaalaansluiting Nederlands Manual de instalaci n y operaci n Fan coils entubados Espa ol Manuale d installazione e d uso Unit fan coil canalizzata Italiano Manual de instala o e de funciona...

Page 2: ......

Page 3: ...2 274 53 29 241 98 579 506 382 510 17 273 53 294 757 17 17 C D 757 29 5 1 D 5 1 1 0 0 17 FWD04 FWD06 FWD08 10 D 646 856 1066 H 223 223 223 FWD12 FWD16 18 1066 1276 296 296 FWD04 10 FWD12 18 A FWD04 FW...

Page 4: ...FWEC1 FWD 04 12 FWEC1 FWD 16 18 EPIB6 UT66000880 UT66000881...

Page 5: ...FWEC2 3 FWD 04 12 FWEC2 3 FWD 16 18 UT66000888 UT66000889...

Page 6: ...FWECSA FWD...

Page 7: ...ning and intended for use in civil comfort applications do not install the unit in rooms where inflammable gases are pre sent do not let water spray directly on the unit install the unit on ceilings o...

Page 8: ...ttachments on the opposite side as follows 1 remove the upper and lower closing panels 1 2 2 remove the condensate tank for the horizontal installation 8 3 loosen the 4 fixing screws of the motor supp...

Page 9: ...ry accessory In order to make the electrical connections you must remove the lower closing panel see figure 6 to access the terminal strip The power cables power supply and control must be routed to t...

Page 10: ...ting If the unit does not work properly first check the points reported in the table below before requesting service If the problem cannot be solved contact your dealer or service centre Symptom 1 The...

Page 11: ...20 C 43 C Spannungstoleranz 10 Grenzwert relative Luftfeuchtigkeit der Raumluft RH 85 nicht kondensierend Auswahl des Installationsortes F r die Klimatisierung der Raumluft und f r den Einsatz f r Anw...

Page 12: ...bschnitte des Lufteinlass und der Auslassrohre sind rechteckig und mit Bohrl chern versehen zur Befestigung der vorhandenen Zubeh rteile Ein rundes vorgeschnittenes Element 100 mm ist auf beiden Seite...

Page 13: ...Verkabelung S mtliche bauseitigen Verdrahtungen und Bauteile m ssen von einem zugelassenen Elektriker installiert werden und den entsprechenden rtlichen und staatlichen Vorschriften entsprechen F hren...

Page 14: ...ng sowie Reini gung bedeutet Energieerhaltung und Kostenersparnis Vorschriften zur Entsorgung Die Demontage der Einheit muss gem den jeweiligen rtlichen und staatlichen Vorschriften erfolgen Fehlerbes...

Page 15: ...s condensation S lection d un emplacement Appareils con us pour la climatisation de l air ambiant et destin s trelis s pour des applications de confort civil ne pas installer l unit dans des locaux o...

Page 16: ...ngeur thermique 10 Fixations de l vacuation d eau de condensation 11 Barrette de raccordement 12 Structure de support de charge Nous vous recommandons d installer les accessoires sur l quipement stand...

Page 17: ...ons expos es directement aux rayons du soleil ou des positions soumises des courants d air chaud ou froid directs Ne placez pas d obstacles sur le chemin qui vous emp cheraient de lire correctement la...

Page 18: ...oyez l air comprim ou la vapeur basse pression sans endommager les ailettes de l changeur thermique Avant de le faire fonctionner en t v rifiez r guli rement l vacuation de l eau de condensation NOTE...

Page 19: ...ieve vochtigheidslimiet van de omgevingslucht RH 85 zonder condensvorming Keuze van de montageplaats installeer het toestel niet in een ruimte met ontvlambare gassen zorg ervoor dat er geen water rech...

Page 20: ...de technische fiches De inlaat en aanvoerleidingen zijn rechthoekig en voorzien van gaten voor de beschikbare accessoires Aan beide zijpanelen van de unit is een op voorhand nagesneden element 100 mm...

Page 21: ...lektricien moet instaan voor het uitvoeren van de lokale bedrading en monteren van de onderdelen Dit moet overeenkomstig de lokale en nationale voorschriften gebeuren Schakel het toestel uit voordat u...

Page 22: ...hadigen Controleer de condensaatafvoer regelmatig voordat u de unit in de zomer gebruikt NOTE Correct en regelmatig onderhoud en reinigen werkt energiebesparend en voorkomt dure reparaties Eisen bij h...

Page 23: ...nados a ser utilizados en aplicaciones de confort civil no instale la unidad en salas con presencia de gases inflamables impida las salpicaduras directas de agua en la unidad instale la unidad en tech...

Page 24: ...3 8 8 Dep sito de agua de condensaci n para montaje en el techo tubo de 3 8 9 Conexiones hidr ulicas del intercambiador de calor 10 Conexiones de descarga de agua de condensaci n 11 Regleta de conexi...

Page 25: ...acceso para realizar el ajuste de las funciones y para detectar la temperatura Procure evitar posiciones en las que el equipo est expuesto a los rayos directos del sol o posiciones en las que el equi...

Page 26: ...n evitando da ar las aletas del intercambiador de calor Antes de operar la unidad en verano compruebe peri dicamente las descargas de agua de condensaci n NOTE El mantenimiento y limpieza adecuada y...

Page 27: ...e Apparecchi progettati per la climatizzazione dell aria ambiente e destinati all utilizzo in applicazioni di comfort civile non installare l unit in ambienti in cui sono presenti gas infiammabili non...

Page 28: ...ambiatore di calore 10 Attacchi scarico condensa 11 Morsettiera 12 Struttura portante Si consiglia di installare tutti gli accessori sull unit standard prima di collocarla nella posizione stabilita fa...

Page 29: ...i soggette a correnti di caria calda o fredda diretta Non mettere alcun tipo di oggetto che ostacoli la corretta lettura della temperatura Collegamenti da effettuarsi in loco Sia i collegamenti elettr...

Page 30: ...pulire con aria compressa o con vapore a bassa pressione senza danneggiare le alette Prima di accenderlo d estate controllare che la condensa sia regolarmente scaricata NOTE Una manutenzione e una pul...

Page 31: ...FWD 4PW17549 3 Daikin Daikin Daikin n n 5 C 95 C n 10 bar n 20 C 43 C n 10 n RH 85 FWD 1 3 180 FWD 1 2 E M4 kit 1 FWD 1...

Page 32: ...2 2 5 1 6 2 3 4 4 4 DF 5 6 6A 6B 7 100 mm FWD 3 AA AB TA DP TWM 14 C TW TA DP 14 C 25 C 75 20 C 20 14 6 C 3 AA AB AA kit 6 1 2 3 4 5 6 DF 7 3 8 8 3 8 9 10 11 12 100 mm 6 1 1 2 2 8 3 7 4 5 4 5 6 4 6 M8...

Page 33: ...FWD 4PW17549 3 3 8 30 mm m AA 90 AB 6 5 mm 3 5 mm 2 9 FWD AA 10 FWD AB kit EDEH IL 3 mm F 6 7 FWD 3 WH 7 BK BU GY GNYE RD WH CN F IL M OFF 3...

Page 34: ...FWD 4PW17549 3 OFF OFF 6 8 8 1 2 1 STOP 0 ON I 2 3 4...

Page 35: ...Selec o do local Aparelhos projetados para a climatiza o do ar ambiente e destinados utiliza o em aplica es de conforto civil n o instale a unidade em salas que contenham gases inflam veis n o permit...

Page 36: ...de calor 10 Anexos para a descarga de condensado 11 Placa de bornes 12 Estrutura de suporte de carga Aconselha se que eventuais acess rios sejam instalados nos equipamento padr o antes de o colocar no...

Page 37: ...os solares bem como posi es sujeitas a correntes de ar quente ou frio N o coloque obst culos em redor do painel para que a medi o da temperatura seja a correcta Liga es el ctricas locais Toda a cablag...

Page 38: ...ifique regularmente as descargas de condensado NOTE A manuten o e limpeza adequadas regulares produzem poupan a de energia e custos menores Exig ncias relativas elimina o A desmontagem da unidade deve...

Page 39: ...FWD 4PW17549 3 Daikin Daikin Daikin 5 C 95 C 10 20 C 43 C 10 RH 85 FWD 1 3 180 FWD 1 EU 2 M4 1 FWD 1...

Page 40: ...2 EU 2 2 5 1 6 2 3 4 4 4 DF 5 6 6A 6B 7 100 FWD 3 AA AB TA DP TWM 14 C TW TA DP 14 C 25 C 75 20 C 20 14 6 C 3 2 3 AA AB AA 6 1 2 3 4 5 6 DF 7 3 8 8 3 8 9 10 11 12 100 6 1 1 2 2 8 3 7 4 5 4 5 6 4 6 M8...

Page 41: ...FWD 4PW17549 3 30 90 6 5 3 5 2 9 FWD AA 10 FWD A EDEH IL 3 F 6 7 FWD 3 WH 7 BK BU GY GNYE RD WH CN F IL M OFF 3...

Page 42: ...FWD 4PW17549 3 OFF OFF 6 8 8 1 2 NOTE Symptom 1 STOP 0 ON I Symptom 2 Symptom 3 4...

Page 43: ...ndensation Val av installationsplats Apparater konstruerade f r klimatkontroll av omgivande luft avsedd f r anv ndning i civila komfortapplikationer Installera inte aggregatet i omgivningar med brandf...

Page 44: ...erna In och utloppens r rdel r rektangul r och f rsedd med h l f r fasts ttning av de tillbeh r som finns tillg ngliga P b da sidorna av aggregatets paneler finns en f rskuren rund del 100 mm f r dire...

Page 45: ...ensst mmer med det nominella str mv rdet som anges p aggregatets m rkskylt Varje aggregat beh ver en brytare IL p str mf rs rjningen med ett avst nd p minst 3 mm mellan ppningskontakterna och en passa...

Page 46: ...ortskaffning Apparaten ska bortskaffas i enlighet med g llande lokal och nationell lagstiftning Fels kning Om aggregatet inte fungerar som det ska ska man f rst av allt kontrollera punkterna i tabelle...

Page 47: ...4PW17549 3 Zandvoordestraat 300 B 8400 Oostende Belgium...

Reviews: