SiEN18-622
Troubleshooting for SkyAir Indoor Unit
Troubleshooting
345
5.10 Malfunction of Suction Air Thermistor
Remote Control
Display
C9
Applicable
Models
FFQ, FCQ, FBQ, FHQ
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by suction air temperature sensor.
Malfunction
Decision
Conditions
When the suction air temperature sensor’s thermistor becomes disconnected or shorted while
the unit is running.
Supposed
Causes
Failure of the sensor itself
Broken or disconnected wire
Failure of indoor unit PCB
Failure of connector contact
Troubleshooting
Check No.02
Refer to P.351
Disconnect the sunction air
temperature sensor (R1T)
from X19A on the indoor unit
PCB and measure the
resistance.
Is the
thermistor normal?
(See note)
NO
YES
(Q0418)
NO
YES
Check contact of connector
Is it normal?
See
Check No. 02
for “Thermistor temperature and resistance characteristics”.
Connect correctly.
Heat exchanger
sensor replacement.
If contact is OK,
replace outdoor unit
PCB.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for FTKS50BVMB
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Page 452: ...SiEN18 622 vi Index ...