SiEN18-622
Specifications
Specifications
19
50Hz 220-230-240V
Note:
1.
H
Refrigerant charge is required. (Chargeless piping length 0m)
Formula for calculation charge : R (kg)
R = Total length (m) of liquid pipe size at
φ
9.5×0.054 +Total length (m) of liquid piping size at
φ
6.4×0.022
2. The data are based on the conditions shown in the table below.
Model
RMKS112EV1A
RMKS140EV1A
RMKS160EV1A
4HP
5HP
6HP
Cooling Capacity
kW
(kcal/h)
11.2 (9,630)
14.0 (12,040)
15.5 (13,330)
Total Indoor Unit Capacity
kW
5.5~14.5
7.0~18.2
8.0~20.8
Power Consumption
W
—
Running Current
A
—
Casing Color
Ivory White
Compressor
Type
Hermetically Sealed Scroll Type
Model
JT100FCVD
Motor Output
(2.2kW/60rps)
kW
2.5
3.0
3.5
Refrigerant
Oil
Model
DAPHNE FVC68D
Charge
L
1.5
Refrigerant
Type
R-410A
Charge
kg
4.0
Air Flow Rate
(H)
m³/min (cfm)
106 (3742)
Fan
Type
Propeller
Motor Output
W
70+70
Running Current
A
0.4+0.4
Power Consumption
W
88+88
Starting Current
A
15.3-14.5-14.3
21.1-20.1-19.8
24.2-23.9-23.6
Dimensions (H×W×D)
mm
1,345×900×320
Package Dimensions (H×W×D)
mm
1,475×925×390
Weight
kg
125
Gross Weight
kg
146
Operation Sound
dBA
52
53
54
Piping
Connection
Liquid
mm
φ
9.5 (Flare Connection)
Gas
mm
φ
19.1 (Brazing Connection)
Drain
mm
φ
18
Heat Insulation
Both Liquid and Gas Pipes
No. of Wiring Connection
3 For Power Supply (Including Earth Wiring), 2 For Interunit Wiring (Outdoor Unit-BP)
Total piping
length
O.U. - BP
m
55
BP - I.U.
m
60
80
90
System Total
m
115
135
145
Max. piping
length
BP - I.U.
m
15
1st Branch - I.U.
m
40
Max. level
difference
O.U. - BP
m
30
O.U. - I.U.
m
30
BP - BP, I.U. - I.U.
m
15
Necessity of Additional Charge
H
kg/m
Necessary
Cooling
Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB
Main Piping : 5m
Branch Piping : 3m
Level difference:0m
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
BP Unit
O
u
tdoor Unit
M
a
in Piping
Br
a
nch Piping
Indoor Unit
(Q014
3
)
Summary of Contents for FTKS50BVMB
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Page 452: ...SiEN18 622 vi Index ...