SiEN18-622
Field Setting
Test Operation
153
Caution
DIP switch Setting after changing the main PCB(A1P) to spare parts PCB
When you change the main PCB(A1P) to spare parts PCB, please carry out the following setting.
Please Attach the Capacity Setting Adapter corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adapter
1
2
3
C
a
p
a
city Cl
ass
4 (112)
5 (140)
6 (160)
CAPACITY
S
ETTING ADAPTER (for 100/J112)
CAPACITY
S
ETTING ADAPTER (for 125/J140)
CAPACITY
S
ETTING ADAPTER (for 140/J160)
Po
s
ition of Att
a
ching the C
a
p
a
city
S
etting Ad
a
pter
Note
X51A
Po
s
ition of Att
a
ching the
C
a
p
a
city
S
etting Ad
a
pter