Basic Control
SiEN18-622
98
Function
Heating Operation
TcS = TcS initial value + KTc2
KTc2 : Correction value by
Δ
D signal in heating.
Δ
D control
Keep the current KTc2
KTc2 = KTc2 + 0.5
KTc2 = KTc2 - 0.5
(Q0
3
97)
KTc2 = 0
(without correction)
Not during compressor frequency PI
control
During compressor frequency PI
control (KTc2 = 0)
Down control by
Δ
D signal
continues 120 sec.
Up control by
Δ
D signal
continues 120 sec.