Field Setting
SiEN18-622
156
Test Operation
No.
Setting item
Description
1
Cool/heat unified
address
Sets address for cool/heat unified operation.
2
Low noise/demand
address
Address for low noise/demand operation
3
Test operation
settings
Used to conduct test operation without making changes
to the PCB and replacing the refrigerant, after the
completion of maintenance.
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10
Defrost changeover
setting
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
12
External low noise
setting / Demand
setting
Reception of external low noise or demand signal
13
AIRNET address
Set address for AIRNET.
16
Setting of hot water
Make this setting to conduct heating operation with hot
water heater.
20
Additional
refrigerant charge
operation setting
Carries out additional refrigerant charge operation.
21
Refrigerant
recovery /
vacuuming mode
setting
Sets to refrigerant recovery or vacuuming mode.
22
Night-time low
noise setting
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on “Starting set” and “Ending
set”.
25
Setting of external
low noise level
Sets low noise level when the low noise signal is input
from outside.
26
Night-time low
noise operation
start setting
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
27
Night-time low
noise operation end
setting
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
28
Power transistor
check mode
∗
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
29
Capacity
precedence setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
30
Demand setting 1
Changes target value of power consumption when
demand control 1 is input.
32
Normal demand
setting
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.
b. “
S
ettin
g
mode 2”
<
S
election of
s
ettin
g
item
s
>
<
S
election of
s
ettin
g
condition
s
>
P
us
h
a
nd hold the MODE (B
S
1)
bu
tton for 5
s
econd
s a
nd
s
et to
“S
etting mode 2
”
.
P
us
h the
S
ET (B
S
2)
bu
tton
a
nd
s
et
the LED di
s
pl
a
y to
a s
etting item
s
hown in the t
ab
le on the right.
P
us
h the RETURN (B
S3
)
bu
tton
a
nd
decide the item. (The pre
s
ent
s
etting
condition i
s b
linked.)
P
us
h the
S
ET (B
S
2)
bu
tton
a
nd
s
et
to the
s
etting condition yo
u
w
a
nt.
P
us
h the RETURN (B
S3
)
bu
tton
a
nd
decide the condition.
P
us
h the RETURN (B
S3
)
bu
tton
a
nd
s
et to the initi
a
l
s
t
a
t
us
of
“S
etting
mode 2
”
.
*
If yo
u b
ecome
u
n
su
re of how to
proceed, p
us
h the MODE (B
S
1)
bu
tton
a
nd ret
u
rn to
s
etting mode 1.
(V2764)
Summary of Contents for FTKS50BVMB
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Page 452: ...SiEN18 622 vi Index ...