2. Instruction
2.1
RMXS Series
Regarding use
Super Multi Plus System air conditioner
Points the customer should be aware of
Comfort
At startup
•
After the power is initially turned on, it will take approx. 10 minutes until startup. Usually the unit will start in 3 minutes.
Heating operation (Not for a unit for cooling only)
•
The colder it is outside or the greater the number of indoor units, the longer the time required from the start of operation until
the emission of warm air (around 35°C). When the outside temperature is -5 to 2°C, the inside temperature is 5 to 10°C, and
total indoor unit combination is 100% capacity, the first startup of all indoor units in the morning will take approximately 20 to
30 minutes.
•
Oil return operation will be performed once every 8 hours to preserve the lubrication of oil to the compressor.
Since operation is switched to cooling cycle during heating operation in order to return the oil, heating operation will not be
possible for around 5 to 10 minutes.
•
When the outside temperature is 28°C or higher, the unit will be set to the standby mode for protection.
Operating noise
At startup
•
During startup, in order to emit warm or cool air as quickly as possible, the sound of refrigerant flowing will be heard for a
short time (1 to 2 minutes) from the outdoor unit.
At shutdown
•
In order to ensure smooth startup the next time this unit is operated, the outdoor unit will continue to operate for around 1
minute after shutdown. (The time of continued operation depends on the outside temperature, capacity of connected indoor
units, and connection pipe length.)
Cooling at low outside temperatures
•
During cooling operation when the outside temperature is 20°C or less, the fan of the outdoor unit will operate at low speed to
preserve capacity and the outdoor unit valve will be opened depending on the pressure conditions, making it more likely that
the sound of refrigerant flowing will be heard.
Defrost (Not vor a unit for cooling only)
•
When the outside unit is performing defrosting operation, the fan of the indoor unit will stop temporarily, and the slight sound
of refrigerant flowing will be heard.
Excessive heating load (Not for a unit for cooling only)
•
During heating operation when the outside temperature is high (15 to 24°C), the fan of the outdoor unit will be operated at low
speed, making it more likely that the sound of refrigerant flowing will be heard from the outdoor unit.
Summary of Contents for FTKS50BVMB
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Page 452: ...SiEN18 622 vi Index ...