Indoor Unit (RA Models)
SiEN18-622
128
Function
7.10 HOME LEAVE Operation
Outline
In order to respond to the customer's need for immediate heating and cooling of the room after
returning home or for house care, a measure to switch the temperature and air volume from that
for normal time over to outing time by one touch is provided. (This function responds also to the
need for keeping up with weak cooling or heating.)
This time, we seek for simplicity of operation by providing the special temperature and air
volume control for outing to be set by the exclusive button.
Detail of the
Control
1. Start of Function
The function starts when the [HOME LEAVE] button is pressed in cooling mode or heating
mode (including stopping and powerful operation). If this button is pressed while the operation is
stopped, the function becomes effective when the operation is started. If this button is pressed
in powerful operation, the powerful operation is reset and this function becomes effective.
The [HOME LEAVE] button is ineffective in dry mode and fan mode.
2. Details of Function
A mark representing [HOME LEAVE] is indicated on the liquid crystal display of the remote
control. The indoor unit is operated according to the set temperature and air volume for HOME
LEAVE which were pre-set in the memory of the remote control.
The LED (Red) of indoor unit representing [HOME LEAVE] lights up. (It goes out when the
operation is stopped.)
3. End of Function
The function ends when the [HOME LEAVE] button is pressed again during [HOME LEAVE]
operation or when the powerful operation button is pressed.
Others
The set temperature and set air volume are memorized in the remote control. When the remote
control is reset due to replacement of battery, it is necessary to set the temperature and air
volume again for [HOME LEAVE].
S
cene <cooling>
Home leaving operation
Normal operation
Normal operation
S
t
a
rt
“
Home le
a
ve oper
a
tion
”
S
top
“
Home le
a
ve oper
a
tion
”
Time
“
Home le
a
ve
oper
a
tion
”
s
et temp.
S
et temp.
S
cene <He
a
ting>
Home leaving operation
Normal operation
Normal operation
S
t
a
rt
“
Home le
a
ve oper
a
tion
”
S
top
“
Home le
a
ve oper
a
tion
”
Time
“
Home le
a
ve
oper
a
tion
”
s
et temp.
S
et temp.
Summary of Contents for FTKS50BVMB
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Page 452: ...SiEN18 622 vi Index ...