SiEN18-622
Special Control
Function
101
3. Special Control
3.1
Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
3.1.1 Startup Control in Cooling Operation
3.1.2 Startup Control in Heating Operation
Thermostat ON
Pressure equalization control
prior to startup
Startup control
STEP1
STEP2
Compressor
0 Hz
57 Hz Unload
57 Hz Unload
+2 steps/20 sec.
(until Pc - Pe>0.39MPa is achieved)
Outdoor unit fan
STEP7
Ta<20
°
C: OFF
Ta
≥
20
°
C: STEP4
+1 step/15 sec. (when Pc>2.16MPa)
-1 step/15 sec. (when Pc<1.77MPa)
Four way valve (20S1)
Holds
OFF
OFF
Main electronic expansion
valve (EV1)
0 pls
480 pls
480 pls
Subcooling electronic
expansion valve (EV3)
0 pls
0 pls
0 pls
Hot gas bypass valve
(SVP)
OFF
OFF
OFF
Ending conditions
•
Pc - Pe<0.3MPa
•
A lapse of 1 to 5 min.
A lapse of 10 sec.
•
A lapse of 130 sec.
•
Pc - Pe>0.39MPa
OR
OR
Thermostat ON
Pressure equalization control
prior to startup
Startup control
STEP1
STEP2
Compressor
0 Hz
57 Hz Unload
57 Hz Unload
+2 steps/20 sec.
(until Pc - Pe>0.39MPa is achieved)
Outdoor unit fan
From starting
~ 1 min. : STEP 7
1 ~ 3 min. : STEP 3
3 ~ 5 min. : OFF
STEP8
STEP8
Four way valve
Holds
ON
ON
Main electronic expansion
valve (EV1)
0 pls
0 pls
0 pls
Subcooling electronic
expansion valve (EV3)
0 pls
0 pls
0 pls
Hot gas bypass valve
(SVP)
OFF
OFF
OFF
Ending conditions
•
Pc - Pe<0.3MPa
•
A lapse of 1 to 5 min.
A lapse of 10 sec.
•
A lapse of 130 sec.
•
Pc>2.70MPa
•
Pc - Pe>0.39MPa
OR
OR
Summary of Contents for FTKS50BVMB
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Page 452: ...SiEN18 622 vi Index ...