SiEN18-622
Field Setting
Test Operation
159
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
Setting item 0 Display contents of “Various setting”
No.
Setting item
LED display
Data display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0
Various setting
9 7 7 7 7 7 7
See below
1
C/H unified address
9 7 7 7 7 7 8
Lower 6 digits
2
Low noise/demand address
9 7 7 7 7 8 7
3
Not used
9 7 7 7 7 8 8
4
Airnet address
9 7 7 7 8 7 7
5
Number of connected indoor units
9 7 7 7 8 7 8
7
Number of connected zone units
(excluding outdoor and BS unit)
9 7 7 7 8 8 8
8
Number of outdoor units
9 7 7 8 7 7 7
11
Number of zone units (excluding
outdoor and BS unit)
9 7 7 8 7 8 8
Lower 6 digits
12
Number of terminal blocks
9 7 7 8 8 7 7
Lower 4 digits:
upper
13
Number of terminal blocks
9 7 7 8 8 7 8
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
8 7 7 8 8 8 7
Malfunction
code table
Refer page
320
15
Contents of malfunction
(1 cycle before)
8 7 7 8 8 8 8
16
Contents of malfunction
(2 cycle before)
8 7 8 7 7 7 7
20
Contents of retry (the latest)
8 7 8 7 8 7 7
21
Contents of retry (1 cycle before)
8 7 8 7 8 7 8
22
Contents of retry (2 cycle before)
8 7 8 7 8 8 7
25
Normal judgment of outdoor units
PC board
9 7 8 8 7 7 8
Lower 2 digits:
87
Abnormal
78
Normal
77
Unjudgement
EMG operation /
backup operation
setting
ON
9 7 7 8 7 7 7
OFF
9 7 7 7 7 7 7
Defrost select setting
Short
9 7 7 7 8 7 7
Medium
9 7 7 7 9 7 7
Long
9 7 7 7 7 7 7
Te setting
H
9 7 7 7 7 8 7
M
9 7 7 7 7 9 7
L
9 7 7 7 7 7 7
Tc setting
H
9 7 7 7 7 7 8
M
9 7 7 7 7 7 9
L
9 7 7 7 7 7 7
c. Monitor mode
<
S
election of
s
ettin
g
item>
<Confirmation on
s
ettin
g
content
s
>
To enter the monitor mode, p
us
h the
MODE (B
S
1)
bu
tton when in
“S
etting
mode 1
”
.
P
us
h the
S
ET (B
S
2)
bu
tton
a
nd
s
et
the LED di
s
pl
a
y to
a s
etting item.
P
us
h the RETURN (B
S3
)
bu
tton to
di
s
pl
a
y different d
a
t
a
of
s
et item
s
.
P
us
h the RETURN (B
S3
)
bu
tton
a
nd
s
witche
s
to the initi
a
l
s
t
a
t
us
of
“
Monitor mode
”
.
*
P
us
h the MODE (B
S
1)
bu
tton
a
nd
ret
u
rn
s
to
“S
etting mode 1
”
.
(V2765)
Summary of Contents for FTKS50BVMB
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump ...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit ...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function ...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300 ...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting ...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix ...
Page 452: ...SiEN18 622 vi Index ...