CTI 2572-A Installation and Operation Guide V1.3
85
HEX
DEC
DESCRIPTION
SOLUTION
connect.
host. Make sure that all IP addresses are properly
set, that the remote host is on line, and that network
cables are connected properly.
240D 9229 CONNECTION
REFUSED
The remote host refused the connection.
If the remote host is a 2572, the maximum number
of TCP connections allowed has been exceeded.
Wait and try again.
240E
9230
REMOTE HOST IS UNREACHABLE
The remote host cannot be found.
This error may occur when the remote host has
been taken out of service. It may also occur if you
have specified an incorrect IP address.
240F
9231
URGENT DATA RECEIVED
The remote host has sent urgent data via TCP. This
feature is not supported by the 2572-A.
The remote device has sent you a message format
that is not supported. If the remote host is a
computer, check to software and network setup.
For additional information, see documentation on
TCP/IP.
2410
9232
OUT OF BAND DATA RECEIVED
You have been sent out of band data via TCP. This
feature is not supported by the 2572-A.
See above.
246E
9326
NITP PROTOCOL ERROR
When the 2572-A sent an NITP message, the
remote device replied with an invalid NITP
message. NITP protocol errors include:
- Odd number of characters received,
- Invalid characters received,
- Checksum error,
- Incorrect character count field.
This error may occur due to communications error
(line noise, etc.) on serial lines. It may also result
from an improperly programmed remote device.
Retry the operation. If the error persists, check out
the remote device.
2470 9328 INVALID OPTION BIT VALUE
The option bit setting is invalid when compared to
the other parameters in the command block.
Correct the option bit setting or change the
conflicting parameters.
If you are using TCP, you cannot set the IP Address
Location bit to 1.
2473 9331 BAD OR MISSING DELIMITER
The
receiving
device detected a bad or missing
delimiter in the command message
This error usually indicates a transient error in the
data link. You should retry the command.
If the receiving node is a computer simulating a
2572-A PLC server, ensure that the software is
correctly processing the message.
If the error persists contact CTI.
2474 9332 BAD BLOCK CHECK CHARACTER
The
receiving
device detected a block check
character error in the command message.
See error code 2473
2475 9333 INVALID TYPE
The
receiving
device reported an invalid TYPE
character in the message.
See error code 2473.
2476 9334 INVALID DATA CHARACTER
The
receiving
device reported an invalid data
character. Only characters 0-9 and A-F are allowed.
See error code 2473.
2477 9335 ODD NUMBER OF CHARACTERS
The
receiving
device reported an odd number of
characters in the message. All CAMP messages
have an even number of characters.
See error code 2473.
2478 9336 INVALID DEVICE CODE
The
receiving
device reported an invalid device
See error code 2473.
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...