CTI 2572-A Installation and Operation Guide
84
PLC Client Error Codes
HEX
DEC
DESCRIPTION
SOLUTION
2401 9217 PROTOCOL
NOT
SUPPORTED
The remote device does not support the TCP/IP
protocol you are requesting.
The protocol may have been disabled in the startup
options of the remote 2572-A Network Server.
Check the remote device.
Check the network address in the command block. If
you are using a PC to emulate a PLC server, ensure
that the network parameters are properly set.
2402
9218
SOCKET TYPE NOT SUPPORTED
The remote device does not support the socket type
you are requesting.
See the previous solution.
2403
9219
NETWORK ADDRESS IN USE
The 2572-A cannot obtain the network address.
This may occur when there is a general problem on
the network. Check the network address you have
specified in the command block. Correct if
necessary. Retry the operation. If the problem
persists contact your network administrator.
2404 9220 CANNOT
ASSIGN
ADDRESS
The 2572-A cannot assign the requested address.
See above. If the problem persists contact CTI.
2405 9221 NETWORK
IS
DOWN
The network you are attempting to use is down.
This may occur when you are attempting to connect
to a remote on another network via a router and the
network has been taken out of service.
First, make sure that you have specified the correct
IP address. Retry the operation. If the problem
persists, contact your network administrator.
2406 9222 NETWORK
IS
UNREACHABLE
The network you are attempting to use is
unreachable.
You have specified a network address for a network
that cannot be found. This probably occurred
because you specified an incorrect IP network
address. Check the entry in the command block and
retry.
If you believe that you are using the correct network
address, contact your network administrator.
2407 9223 NETWORK
CONNECTION
ABORTED
The remote device (host) aborted the connection.
This may occur if the remote host encountered a
problem with TCP data transmission where recovery
was not possible. You should attempt to create the
connection again. If the problem persists, check the
remote host.
2408
9224
CONNECTION RESET BY PEER
The remote device has reset the connection.
See error code 2407.
2409 9225 INSUFFICIENT
BUFFER
SPACE
There is insufficient buffer space to hold the
message.
This could occur when the remote host has sent
more data than the negotiated buffer space. Retry
the operation. If the problem persists, contact CTI.
240A
9226
SOCKET NOT CONNECTED
The socket you are attempting to use is not
connected to the remote host.
The socket may have been previously disconnected
from the remote host work by a network error or
because the remote host closed the connection.
Create the network connection again and retry.
240B
9227
ATTEMPT TO SEND AFTER SOCKET HAS BEEN
SHUT DOWN
You are attempting to send data to a socket that has
been closed
See above.
240C
9228
CONNECTION TIMED OUT
The remote host is not responding to an attempt to
Attempt to create the network connection again. If
the problem persists check the status of the remote
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...