CTI 2572-A Installation and Operation Guide V1.3
83
HEX
DEC
DESCRIPTION
SOLUTION
exceeded the maximum allowable value.
238E
9102
INVALID STARTUP OPTIONS
The Startup Options word contains an invalid
combination of bits.
Correct the command block and re-execute the
command.
2397 9111 UNKNOWN
COMMAND
The protocol manager received a command number
that is not valid.
Ensure that Offset 1 in the Command block contains
a valid Command Code.
Check that the Command Slot points to the correct
V memory Address for the Command Block.
Make sure that you have started the correct protocol
manager and that you are using the correct
connection number.
239E
9118
PROTOCOL MANAGER BUSY
The protocol manager received a new command
prior to completing the previous command.
You can cause this error by using two command
slots to send concurrent commands to the same
connection number.
Don’t do this.
239F
9119
INVALID CONNECTION NUMBER
The command block contained an invalid connection
number.
Change the connection number in the command
block to a valid number. See the documentation on
the specific command block.
23AB
9131
SERVER ALREADY STARTED
The PLC logic attempted to start another copy of the
server on the same physical port.
If the error occurs while processing the Start
Network Server Command, the Network Server was
already started. Only one copy of the server is
required to service multiple clients.
This is caused by a PLC logic error. It usually
occurs when you are triggering the command more
than once.
It also may occur when you AutoStart the network
server and also try to start the network server from
PLC logic.
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...