SYMPTOM
PROBABLE CAUSE
CORRECTIVE ACTION
DHCP) and set the Module ID switches to
the appropriate setting. Then reset the
module.
OR
Set the module startup switch to the PLC
Start position and use the PLC interface to
set the IP parameters (see
Section
4.2.
Start Network Server Command Block
)
MS LED is Steady Green,
NS LED is Off
The module is waiting on the PLC to
start the network server.
Ensure the PLC is in run mode and that the
2572-A is properly entered in the PLC I/O
configuration.
Check the PLC logic. See
Section
8.7. PLC
Logic Problems.