CTI 2572-A Installation and Operation Guide V1.3
59
The S
OURCE
E
LEMENT
specifies the 505 PLC Tag Name. We want to read a 16 bit unsigned integer
into a 32 bit signed Control Logix tag, so we will use the tag type VE. Since we want to start reading
at V memory location 501, the complete Tag Name is VE501.
We want to read a block of 100 registers, so the N
UMBER OF
E
LEMENTS
will be set to 100.
The D
ESTINATION
E
LEMENT
specifies the Control Logix tag that will store the results of the read
message. This is the tag we defined earlier. Since this is an array, we will specify that first value
returned will be stored in array element 0. Additional values will be stored in subsequent array
elements.
Communication Tab
The Communication Tab is used to specify the message routing and destination IP address.
The path specifies the route from the controller to the destination. In this case, we will send the
message to the backplane (1), to the Ethernet module located in slot 3, out the Ethernet port (2), to the
2572-A module whose IP address is 192.184.177.225.
The C
ACHE
C
ONNECTIONS
box is checked to keep the TCP connection established after the message
is completed. If you don’t check this box, the Control Logix will close the TCP connection after each
message transaction is complete. Continually opening and closing the TCP connection adds
unnecessary overhead and reduces performance.
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...