CTI 2572-A Installation and Operation Guide V1.3
71
Within each set of four Command Status bits:
•
The first bit is the Command Error bit,
•
The second bit is the PLC Error bit,
•
The third bit is the Command Busy bit,
•
The fourth bit is the Abort Busy bit.
Therefore, to set a command trigger only (uncoupled mode) for the first command slot, set WY4 to
hex 2000. To set the command trigger for the second slot, set the WY4 to hex 0200. To set the error
acknowledge for the third Command Slot, set WY4 to hex 0080.
When you are using PLC logic to control the PLC, it is often useful to display the module WX/WY
words, parts of the command blocks, and sections of the format specifications as a chart. Following
is an example chart.
LOCATION
STATUS LOCATION
STATUS LOCATION
STATUS
WX1 =
HEX
V100
=
HEX
V300
=
HEX
WX2 =
HEX
V101
= INTEGER
V301
= INTEGER
WY3 =
HEX
V102 =
INTEGER
V302 =
INTEGER
WY4 =
HEX
V103 =
INTEGER
V303 =
INTEGER
WY5
= INTEGER V104
= INTEGER
V304
= INTEGER
WY6
=
INTEGER
WY7 =
INTEGER
V120
=
HEX
V2000
= INTEGER
WY8 =
INTEGER
V121 =
INTEGER
V2001
= INTEGER
V122
=
INTEGER
V2002
= INTEGER
V123
=
INTEGER
V2003
= INTEGER
V124
=
INTEGER
V2004
= INTEGER
V2005
= INTEGER
The above chart allows you to examine at the value of the module status word (WX1), the command
status word (WX2), the module control word (WY3), and the command control word (WY4) in hex.
It also displays the command slots (WY5-WY8) as integers. V100, V120, and V140 are assumed to
contain command blocks you are using; this display shows the first four words, including the error
word in hex format. V2000 is assumed to contain data you wish to monitor. Change the display to
match your setup.
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...