CTI 2572-A Installation and Operation Guide V1.3
95
WX2 and WY4 Relationships
The following illustrates the relationship between the first four bits in WX2 and WY4. This
relationship applies to the other three sets of bits.
Word
Bit 1
Bit 2
Bit 3
Bit 4
WX2
CMD Err
PLC Err
CMD Busy
Abort Busy
WY4
ERR Ack
CMD Mode
CMD Trigger
Abort Trigger
Error Processing Bits
The module will set CMD
E
RR
any time an error occurs in processing a command. The module will
also set PLC
E
RR
if a valid Command Block cannot be read from V memory. After setting the error
bits, the module will halt processing on this command. The PLC acknowledges the error by setting
ERR
A
CK
.
When the module sees E
RR
A
CK
go high, it aborts the command, clears the error bits, and
is ready to accept another command trigger for this slot.
Command Processing Bits
The PLC sets the CMD
M
ODE
bit to select whether Coupled Mode or Uncoupled Mode is used. The
PLC sets the CMD
T
RIGGER
to initiate the command. When the module begins command processing,
it sets the CMD
B
USY
bit. The CMD
B
USY
bit will remain on until the module has competed
processing the command.
Abort Processing Bits
The PLC can set the ABORT
T
RIGGER
to request the module to abort a command that is in process.
When the module starts the process of aborting a command, it raises the A
BORT
B
USY
bit. When the
process is complete, it lowers A
BORT
B
USY
(and also CMD
B
USY
).
The timing diagrams in this appendix describe the interaction of the various Command Control and
Command Status bits.
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...