CTI 2572-A Installation and Operation Guide
26
4.2. Start Network Server Command Block
Offset
Description
Hex
Value
Decimal
Value
0
Command Error Word
0000
0
1
Command (Start Network Server)
0004
4
2
Connection Number (19291 - 19299)
4B62
19298
3
Protocol Manager Number
0023
35
4
Startup Option Bits (see description below)
0000
0
5
TCP Keep Alive Interval in Seconds (0=default = 60)
(Set to 65000 or greater to disable Keep Alive)
0000
0
6
IP Address of this Module (High 16 bits)
7
IP Address of this Module (Low 16 bits)
8
TCP / UDP Port Number
05E1
1505
9
IP Address of Default Router (High 16 bits)
10
IP Address of Default Router (Low 16 bits)
11
Max Number of TCP Connections (0=default)
0000
0
12
Subnet Mask (High 16 bits)
13
Subnet Mask (Low 16 bits)
14
IP Multicast Receive Address (High 16 bits). If you do not
want to receive multicast, set this value to 0.
0000 0
15
IP Multicast Receive Address (Low 16 bits). If you do not
want to receive multicast, set this value to 0.
0000 0
Offset 0
Error Word
- Set to 0 so that any previous error code is cleared.
Offset 1
Command Code
- The Command for Start Network Server is 4.
Offset 2
Connection Number
- You should set this to number in the range of 19291 to 19299
to prevent inadvertent conflict with any client connections you may create. The
value of 19298 is used in CTI examples.
Offset 3
Protocol Manager Number -
Protocol Managers control the operation of the serial
and network ports. Protocol Manager 35 (23 hex) selects the PLC Network Server.
Offset 4
Startup Option Bits
- These bits allow you to configure certain options for the PLC
server. The bits are used as follows:
Bit 1
Bit 2
Bit 3
Bits 4-16
Used by CTI 2572
module, ignored by 2572-
A.
Used by CTI 2572 module,
ignored by 2572-A.
Used by CTI 2572 module,
Ignored by 2572-A.
Reserved
(set to 0)
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...