HEX
DEC
DESCRIPTION
SOLUTION
response message
027C
636
BAD BLOCK CHECK CHARACTER
The 2572-A found a bad block check character in
the response message.
See error code 027A.
027D 637 INVALID
TYPE
The 2572-A detected an invalid TYPE character
in the message sent from the remote device.
See error code 027A.
027E
638
INVALID DATA CHARACTER
The 2572-A detected an invalid data character in
the message sent from the remote device. Only
characters 0-9 and A-F are allowed.
See error code 027A.
027F
639
ODD NUMBER OF CHARACTERS
The 2572-A detected an odd number of
characters in the message sent from the remote
device. All CAMP messages have an even
number of characters.
See error code 027A.
0280
640
UNKNOWN ERROR CHARACTER
The response contained an unknown error
character.
This error is probably caused by an improperly
programmed server node. If the server is a PLC
emulating a 2572-A server, review the code and
correct as required. If the server is another 2572,
contact CTI.
0282
642
INVALID WORD COUNT
The response contained an invalid word count
This error is probably caused by an improperly
programmed server node. If the server is a PLC
emulating a 2572-A server, review the code and
correct as required. If the server is another 2572,
contact CTI.
0283 643 INVALID
ADDRESS
The command contained a memory address of 0.
The minimum CAMP address is 1. Enter the correct
value for the memory address.
0284 644 INCOMPLETE
WRITE
The actual number of words written does not
match the requested number of words.
The actual number of words written is contained
in the response message from the remote device.
This error is probably caused by an improperly
programmed server node. If the server is a PLC
emulating a 2572-A server, review the code and
correct as required.
If the server is another 2572, contact CTI
028B
651
INVALID IP ADDRESS
The command cannot be used with a multicast
address.
Change the IP address to a unicast address or
change the command to one that supports multicast.
0290
656
INVALID ADDRESS CLASS
The address class is not supported by the server
See error 0284 above.
0292
658
MESSAGE ID MISMATCH
The response message contained an ID field
which did not match the ID field in the command.
This error could be caused by a timeout value which
is too short followed by an attempt to re-send.
Therefore, by the time the response to the first
command arrives, you have already sent a second
command. You may correct this condition by
increasing the timeout value.
This may also be caused by an improperly
programmed server. If the server is a PLC emulating
a 2572-A server, review the code and correct as
required.
029C
668
ETHERNET TRANSMISSION ERROR
The Ethernet port was unable to send the packet.
If the problem persists, Contact CTI
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...