CTI 2572-A Installation and Operation Guide
16
may be changed by depressing the increment/decrement button with a small object, such as the tip of
a ballpoint pen.
NOTE:
The Module ID switches are read at module startup. If you change the switch position after startup,
you must reset the module before the setting will take effect.
2.6. Physical Installation
To insert the module into the I/O base, hold the top and bottom of the bezel and slide the module
carefully into the slot, pushing it all the way into the base. If you have inserted the module correctly,
you will feel a slight increase in resistance as the module mates with the base backplane connector.
Once the module is fully seated in the slot, tighten the captive screws at the top and bottom to hold
the module in place. To remove the module from the I/O base, loosen the captive screws, then move
the module. Take care not to damage the connector at the back of the module when inserting or
removing the module.
2.7. Connecting the Ethernet Cable
Insert the 8 pin (RJ-45) plug on your unshielded twisted pair cable into
the RJ-45 jack on the 2572. Push the plug into the jack until the plug
clicks into place. Attach the other end of the cable to an Ethernet hub
or switch hub.
2.8. Initial Power On
Turn on the base power supply. The module should perform a startup
sequence, during which the LEDs will change states as described in CHAPTER 3. MODULE
OPERATION.
After the module completes startup, observe the state of the Module Status (MS) and Network Status
(NS) LEDs and compare to the table below.
Startup Option
LED States
Condition / Action
MS – Steady Green
NS – Steady Green
IP Parameters set and Network Server Started.
Proceed with module check out procedure.
All Methods
MS – Steady Green
NS – Solid Red
Another device on the network is using this IP address.
Although the module will function, you must resolve the conflict
to avoid unpredictable results.
MS – Steady Green
NS – Off
Network Server not Started- Waiting on PLC
Ensure that the PLC is in Run Mode, the module is configured
in the I/O base, and that the correct PLC program is loaded.
The program must contain a Start Network Server Command
Block as associated logic.
PLC
Start
Other States
See APPENDIX A. 2572-A LED INDICATORS
AutoStart from
EEPROM
MS – Flashing Red
NS – Flashing Red
Invalid or Missing IP address in EEPROM
This may occur the first time you use the module because
nothing has been written to EEPROM. See the next section
Figure 7. Ethernet Connection
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...