CTI 2572-A Installation and Operation Guide
90
Command Processing Modes
You can specify how the module command execution is synchronized with the PLC logic by
setting the Command Mode bit in WY4. The Command Mode bit is described in detail later in this
appendix. You can select either
coupled
mode or
uncoupled
mode.
Coupled Mode Processing
Coupled Mode provides for tight "handshaking" between the module and the PLC. When the
PLC triggers the command, the module will execute the command
only once.
The module
will then wait for acknowledgment from the PLC before allowing the command to be
triggered again. Coupled mode is useful for initiating transfers that must be done exactly one
time per PLC event (such as Starting the Network Server).
Uncoupled Mode Processing
Uncoupled Mode does not require a handshaking sequence from the PLC. When Uncoupled
Mode is selected, the module will execute the command continuously as long as the
command trigger is set. Uncoupled mode is useful for providing continuous updates of PLC
data.
Command Processing Procedure
Following is the typical procedure used to initiate a module command:
•
Set up the Command Block(s) in V memory using your PLC programming software
•
Load the command slot(s) with the address of the Command Block(s).
•
Set the applicable command trigger and mode bits in WY4.
•
Monitor the status of the command processing using WX2.
Summary of Contents for 2572-A
Page 8: ......
Page 16: ......
Page 28: ......
Page 32: ......
Page 60: ......
Page 84: ......
Page 96: ......
Page 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Page 112: ......
Page 116: ......
Page 126: ......
Page 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...