CRS-500 1:N Redundancy System
Revision 4
Installation
4–2
MN-CRS-500
To inspect the shipment, do these steps:
1.
Keep all shipping materials.
2.
Check the packing list to make sure the shipment is complete.
3.
Inspect the equipment for damage. If damage exists, immediately contact the carrier and
Comtech EF Data to submit a damage report.
4.
Read the manual.
Proceed to
Section 4.2 Install the CRS-500 1:N Redundancy System Into a Rack Enclosure
.
4.2
Install the CRS-500 System Into a Rack Enclosure
Chapter 5. CABLES
AND
CONNECTIONS
CORRECT GROUNDING PROTECTION IS REQUIRED – Connect the ground studs,
located on the rear panel of the components, to a power system that has separate
ground, line and neutral conductors. Do not operate the system without a direct
connection to ground.
The rack must be connected to a suitable earthing connection at all times. You must
connect the rack ground bar to a suitable earthing demarcation point.
CORRECT AIR VENTILATION IS REQUIRED – In a rack system where there is high heat
discharge, provide forced-air cooling with top- or bottom-mounted fans or blowers.
Make sure there is adequate clearance inside the enclosure, especially at the sides, for
air circulation and ventilation.
Air temperature inside the rack enclosure should
never
exceed 50
°
C (122
°
F).
If there is any doubt, contact Comtech EF Data Product Support during normal
business hours.
Figure 4-2
shows an example of a complete CRS-500 1:N Redundancy System rack configuration.
The standard
CRS-500 CSU
is constructed as a 1RU-high, rack-mounting chassis that may also
be free standing. Rack handles are provided to facilitate removal and placement into a rack.
Install the CSU, using the front panel mounting holes
only,
into the front of the rack.
The standard
CRS-500 DSU
mounts into the back or on top of the rack in one of four
configurations. As shown in Figure 4-3
and Figure 4-4, the user can use the KT-0000072
CRS-500 DSU Rack Mounting Kit (Figure 4-5) to install the DSU module as needed, positioning
or hinging the unit outward to permit convenient access to the RMIs/TMIs for cable connections
between the DSU, CSU, ISU, and the modems.
Mount the optional
CRS-280/280L ISU
into the back or on top of the rack.
Once you install all CRS-500 1:N Redundancy System components, the configuration is now ready
to be interconnected as specified in
Chapter 5. CABLES
AND
CONNECTIONS.
Summary of Contents for CRS-500
Page 24: ...CRS 500 1 N Redundancy System Revision 4 Preface x MN CRS 500 Notes...
Page 38: ...CRS 500 1 N Redundancy System Revision 4 Introduction 1 14 MN CRS 500 BLANK PAGE...
Page 60: ...CRS 500 1 N Redundancy System Revision 4 Installation 4 6 MN CRS 500 BLANK PAGE...
Page 219: ......
Page 220: ...2114 WEST 7TH STREET TEMPE ARIZONA 85281 USA 480 333 2200 PHONE 480 333 2161 FAX...