Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
87
BINARY INPUT
ForceBlock del
FORCE BLOCK
Protection
closed
BINARY INPUT
Prot. block type = Force block
closed
active
active
inactive
BinInpDelayX
Overspeed
[ % ]
Threshold for engine over speed protection.
Step:
1% of
Nominal RPM
Range:
0 – 200%
Hint:
Engine params
:
Starting RPM
value is checked as under-speed level when engine is running.
Max+CylDifPmin [
°
C ]
Max+CylDifPmin = Maximum positive Cylinder temperature Difference at minimal gen-set Power level.
Maximum positive deviation of one cylinder temperature from the average at the
PminCylDifEval
load. Alarm
can be activated depending on Block type (set in GenConfig ->Software configuration->Analog inputs) – all
the time or after some time after start (depends on
RunOnlyBlkDelX
time).
Step:
1
°
C
Range:
0 - 32000
°
C
Max-CylDifPmin [
°
C ]
Max-CylDifPmin = Maximum negative Cylinder temperature Difference at minimal gen-set Power level.
Maximum negative deviation of one cylinder temperature from the average at the
PminCylDifEval.
load.
Alarm can be activated depending on Block type (set in GenConfig ->Software configuration->Analog inputs)
– all the time or after some time after start (depends on
RunOnlyBlkDelX
time).
Step:
1
°
C
Range:
0 - 32000
°
C
Max+CylDifPnom
[
°
C ]
Max-CylDifPnom = Maximum positive Cylinder temperature Difference at nominal gen-set Power level.
Maximum positive deviation of one cylinder temperature from the average at the
Nomin power
. Alarm can be
activated depending on Block type (set in GenConfig ->Software configuration->Analog inputs) – all the time
or after some time after start (depends on
RunOnlyBlkDelX
time).
Step:
1
°
C
Range:
0 - 32000
°
C
Max-CylDifPnom
[
°
C ]
Max-CylDifPnom = Maximum negative Cylinder temperature Difference at nominal gen-set Power level.
Maximum negative deviation of one cylinder temperature from the average at the
Nomin power
. Alarm can
be activated depending on Block type (set in GenConfig ->Software configuration->Analog inputs) – all the
time or after some time after start (depends on
RunOnlyBlkDelX
time).
Step:
1
°
C
Range:
0 - 32000
°
C
PminCylDifEval
[ kW – MW* ]
Minimum gen-set Power for Cylinder temperature Difference evaluation. The protection is not evaluated, if
the gen-set power is lower than this limit.
Step:
0,1 kW / 1 kW / 0,01 MW*
Range:
0,0 kW –
Nominal power*
*Note:
The actual setpoint units and range depend on setting of the Power format (see GenConfig manual).