BinInp delay 1
[ s ]
Binary input protection is activated when input is closed for longer time than
BinInp delay 1
. To use this
delay, Binary input must be configured in GenConfig for Property – Delay = BinInp delay 1.
Step:
0,1s
Range:
0,0 – 600,0 s
Force value possibility: Yes
BinInp delay 2
[ s ]
Binary input protection is activated when input is closed for longer time than
BinInp delay 2
. To use this delay
Binary input must be configured in GenConfig for Property – Delay = BinInp delay 2.
Step:
0,1s
Range:
0,0 – 600,0 s
Force value possibility: Yes
BinInp delay 3
[ s ] (FV)
Binary input protection is activated when input is closed for longer time than
BinInp delay 3
. To use this delay
Binary input must be configured in GenConfig for Property – Delay = BinInp delay 3.
Step:
0,1s
Range:
0,0 – 600,0 s
Force value possibility: Yes
Hint:
BinInp delay
is active only for Binary inputs configured as protection.
If these setpoints are not used, default BI delay is 0,5s.
BINARY INPUT
BinInp delay
physical
BINARY INPUT
Internal value
DriveConfig: I/O, Property, Protection active =
Opened
opened
ForceBlockDel1
[ s ]
ForceBlockDel2
[ s ]
ForceBlockDel3
[ s ] (FV)
Delays for Force block protection activation after the corresponding Binary input Force block is opened.
Protection deactivation is without delay. Protection is activated/deactivated independent on engine running
or not running state – it depends only on the corresponding Force block X input.
Step:
0,1s
Range:
0,0 – 60,0 s
Force value possibility: Yes