Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
76
ConvCoefPulse1 - 4
[ ]
This setpoint adjusts the rate of increasing of the PulseCounter2 – 4 (integrating internal counters that can
be seen at PulseCounter2-4). The setpoint assigns number of pulses (
BI:PulseCounter2 – 4
) to increase the
PulseCounter integrating value by 1.
Step:
1/X
Range:
1 – 65000 1/X
Example:
Number of pulses on the physical input BI: PulseCounter1: 10
ConvCoefPulse1 = 2
Value of the PulseCounter1 integrating counter: 5
Comms settings
Gen-set name
User-defined name, used for controller identification at remote connections.
Gen-set name
is max 15
characters long and has to be entered using PC software.
Hint:
The setpoint can be changed using PC SW only (e.g. InteliMonitor). Gen-set name isn’t affected by
GenConfig SW.
Contr. address
[ ]
Controller CAN bus and RS-485 identification number. Each controller in the group has to have its own
unique number.
Step:
1
Range:
1 to 32
Hint:
When opening Direct or Modem connection to the controller (using PC monitoring/control SW), the
Contr.
address
has to correspond to the Gen-set setting in PC SW.
RS232(1) mode
[ DIRECT / MODEM (HW) / MODEM (SW) / MODBUS-
DIRECT / MODBUS-MDM(HW) / ECU LINK ]
Communication protocol selection for RS232(1) line.
DIRECT:
Connection to a local PC running InteliMonitor. RS232 or RS485 (with internal or
external converter) lines can be used. Set this also for IG-IB connected via RS232 line.
MODEM (HW):
Analog/GSM/ISDN modem connection. Select this for standard modems with HW flow
control. If selected and no CTS signal is detected, communication may not work
correctly.
MODEM (SW):
Analog/GSM/ISDN modem connection. Select this for modems without HW flow control
– controller will use SW flow control signals XOn, Xoff, so only TxD and RxD signals
need to be connected between the controller and the modem.
MODBUS-DIRECT: Modbus protocol for direct connection to PLC / external SCADA terminal.
Communication speed can be selected via setpoint
RS232(1)MBCSpd
.
MODBUS-MDM(HW):Modbus protocol for modem (remote) connection to PLC / external SCADA terminal.
Communication speed can be selected via setpoint
RS232(1)MBCSpd
.
ECU LINK:
Port redirected to connect the ECU with special (not J1939) interface, e.g. Cummins
Modbus.
Hint:
Detail description of Modbus protocol see in Communication guide.
ECU LINK mode can be selected only at RS232(1) port.
RS232(2) mode
[ DIRECT / MODEM (HW) / MODEM (SW) / MODBUS-
DIRECT / MODBUS-MDM(HW) / ECU LINK]
Communication protocol selection for RS232(2) line.