Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
30
Bus frequency
BP
Gener protect
:
Gen >f; Gen <f; Gen V del
Default - configurable
Reverse power (UnivState 1)
BOC
Gener protect
:
Reverse power; ReversePwr
del
Batt <V, Batt >V (UnivState 2)
Wrn
Analog protect
:
Batt >V; Batt <V; Batt V del
EarthFaultCurr (UnivState 5)
BOC
Gener protect
:
EarthFaultCurr; EthCurr del
Gen Current unbalance
BOC
Gener protect
:
Gen I unbal; Gen I unb del
Gen Voltage unbalance
BOC
Gener protect
:
Gen V unbal;Gen V unb del
Bus Voltage unbalance
BOC
Gener protect: BUS V unbal; Bus Vunb del
Bus voltage and frequency protections - limits and indications
Basic settings
:
VoltProtSelect = PHASE-NEUTRAL
Gener protect
:
Gen >V
BOC
Gen <V BOC
Gen >V Sd
Gen V del
Gen >f
Gen <f
Gen f del
Bus V L1-N
Bus freq
Bus V L2-N
Bus V L3-N
Basic settings
:
VoltProtSelect = PHASE-PHASE
Gener protect
:
Gen >V
BOC
Gen <V BOC
Gen >V Sd
Gen V del
Gen >f
Gen <f
Gen f del
Bus V L1-L2
Bus V L2-L3
Bus V L3-L1
Bus freq
Generator voltage and frequency protections - limits and indications
Basic settings
:
VoltProtSelect = PHASE-NEUTRAL
BOC L1 under
BOC L2 under
BOC L3 under
BOC L1 over
BOC L2 over
BOC L3 over
Gen V L1-N
BOC fg under
BOC fg over
Gen freq
Gen V L2-N
Gen V L3-N
Gener protect
:
Gen >V
BOC
Gen <V BOC
Gen V Sd
Gen V del
Gen >f
Gen <f
Gen f del