Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
37
Gen-set operation states
Gen-set can operate in following states
G
EN
-
SET STATE
D
ESCRIPTION
Init
Controller is powerd up and configuration setting is initialized
Not ready
Gen-set is not ready to start or is not allowed to start
Ready
Gen-set is ready to run, all condition for start are fulfilled
Prestart
Prestart sequence in process. From closing of Prestart output to closing
of Starter output
Cranking
Engine is cranking and the starter output is closed
Pause
Pause between start attempts is counting down
Starting
Starting RPM is reached
Running
Gen-set is running and waiting for GCB connection
Warming
Gen-set is running in parallel operation and gen-set load is reduced to
Warming load
Soft load
Gen-set power is ramping up
Loaded
Gen-set is loaded
Soft unld
Gen-set power is ramping down
Cooling
State after GCB was opened and engine is not stopped
Stop Engine
is
stopped
Shutdown
Shutdown alarm activated
Ventil
Gas engine – ventilation of unburned fuel when stop command comes
during cranking with gas
SDVentil
Gas engine – ventilation of unburned fuel after unsuccessful start attempt
Off load
GCB is opened, gen-set keeps running on nominal RPM
Emerg man
Emergency manual state
Gen-set operation states