55
WrongPhSeq
Binary output
WrongPhSeq
is active when at least one of following conditions is fulfilled: Generator, (Mains,
Bus) phase is inverted or wrong generator (mains, bus) phase sequence or opposed generator phase
sequence is detected.
AllAvailGS run
The output gets closed if all gen-sets available to take part in PMS are running and loaded. All gen-sets
having the same logical group (
Pwr management
:
Control group
) as this controller has are cons
gen-sets from other logical groups if those are currently linked with controller’s logical group (using
GroupLink feature).
InMainsParal
This LBO indicates that controller (or logical group, which the controller is member of) is connected to the
mains. It means that there exists a way across MCB (IM-NT-MCB application) or MCB+MGCB (IM-NT-
MGCB application) to the controller. It is possible to configure this signal as MCB feedback of the controller,
what can be useful for complicated applications with higher amount of mains.
Hint:
This signal works correctly only if IM-NT is used as the MCB/MGCB control device.
TimerAct 1-4
TimerAct 5-8
TimerAct 9-12
TimerAct 13-16
These outputs are active if at least one of their assigned timer module channels gets active. Timer module
channels are organized into groups of four.
TimerActiveCom
This output is a logical OR (Com = Common) of the outputs TimerAct 1-4, 5-8, 9-12, 13-16. It gets active if
any timer module channel is active.
kWh pulse
The pulse with 100 miliseconds width is generated after each kWh.
Engines swapped
The output generates 100 ms pulse in case that two gen-sets exchange their priorities due to difference
between Maximal running hours and Minimal running hours value (active when
Pwr management
:
#PriorAutoSwap
set to RUN HOURS EQU).
Binary outputs – Fixed protection outputs
Alarm
The output closes if any alarm comes up. It opens if FAULT RESET is pressed. The output closes again if a
new fault comes up.
Alarm flashing
If any alarm comes up, the output starts periodic closing/opening with period 1s/1s. It opens and stays open
if FAULT RESET is pressed.
Horn
The output closes if any alarm comes up. It opens if FAULT RESET or HORN RESET is pressed or if
Engine protect:
Horn timeout
has elapsed. The output closes again if a new fault comes up.