Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
29
Default protections in MINT
Fix – firmware based protections
E
NGINE
P
ROTECTION
C
ORESPONDING SETPOINTS
Overspeed
SD
Engine protections: Overspeed
Underspeed
SD
Engine params
:
Starting RPM
Generator:
IDMT overcurrent
BOC
Basic settings
:
Nomin current
;
Gener
protect
:
2Inom del
IDMT Active power
BOC
Gener protect
:
OverldStrtEval;
2POvrldStrtEvDel
Shortcurrent BOC
Gener protect
:
Ishort; Ishort del
Generator voltage: Ug1>, Ug1<, Ug2>,
Ug2<, Ug3>, Ug3<
BOC
Gener protect
:
Gen >V BOC; Gen <V BOC;
Gen V del.
Generator voltage: Ug1>>, Ug2>>, Ug3>>
Sd
Gener protect
:
Gen >V Sd; Gen V del.
Generator frequency: fg<, fg>
BOC
Gener protect
:
Gen >f; Gen <f; Gen V del
Bus:
Bus voltage
BP
Gener protect
:
Gen >V BOC; Gen <V BOC;
Gen V del.