Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
23
“Engine started” conditions
-
Engine speed (RPM) >
Starting RPM
or
-
AI: Oil press >
Starting POil
or
-
D+ terminal active for minimum 1s or
-
BI: RunIndication 1 or 2 or 3 = active or
-
Generator voltage > 25% of
GenNomV
(any phase)
“Engine running” conditions
-
RPM
>
Engine params
:
Starting RPM
or
-
Analog input Oil pressure >
Engine params
:
Starting POil
or
-
D+ terminal active and
Engine params
:
D+ function
= ENABLED or
-
Active Binary input RunIndication1 or
-
Active Binary input RunIndication2 or
-
Active Binary input RunIndication3 or
-
Vgen > 15 V (any phase).
“Still engine” conditions
-
Engine speed (RPM) = 0 and
-
AI: Oil press <
Starting POil
and
-
D+ terminal not active and
-
BI: RunIndication 1 and 2 and 3 = not active and
-
Generator voltage < 15V (all phases) and
-
Generator frequency = 0 Hz and
-
if all above conditions are fulfilled, additional 2s delay is necessary to confirm “still engine”
Note:
If any of the functions not used (e.g. BI RunIndication3 not configured), it’s state is omitted in the evaluation.
This is not valid for RPM comparisons, this condition is always active.
PLC functions
For PLC functions description see IGS-NT-2.6-Application guide.pdf.