Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
45
ExtValue1 up
ExtValue2 up
ExtValue3 up
ExtValue4 up
Active binary input causes increasing of the corresponding
ExtValueX
value. The rate of change is given by
the setpoint
ExtValueX rate
. If the
ExtValueX
reaches the
ExtValueXHiLim
, the further input request is
ignored.
ExtValue1 down
ExtValue2 down
ExtValue3 down
ExtValue4 down
Active binary input causes decreasing of the corresponding
ExtValueX
value. The rate of change is given by
the setpoint
ExtValueX rate
. If the
ExtValueX
reaches the
ExtValueXLoLim
, the further input request is
ignored.
Hint:
If at least one of the inputs (
ExtValueX up
/
ExtValueX down
) is configured for the particular
ExtValueX
, the
external set commands to the same value are ignored.
ExtValue1reset
ExtValue2reset
ExtValue3reset
ExtValue4reset
Active binary input causes
ExtValueX
to be reset and held at its default value, given by the setpoint
ExtValueXdeflt
.
Hint:
These inputs, if configured, do not block the external set commands (in contrast to
ExtValueX up
/
ExtValueX
down
inputs). However, if the reset input is activated, the corresponding
ExtValueX
is reset to its default
(
ExtValueXdeflt
) value. This default value is kept in
ExtValueX
until the reset input is deactivated, and the
external set commands received meanwhile are ignored.
Pulse Counter
Hint:
Pulse width (both high/low levels) must be at least 100 ms in order to be correctly sensed!
Conversion ratio can be selected using the setpoints
ConvCoefPulse
. The converted values are visible in
statistics – values
PulseCounter
. These values can be reset using Statistics window in InteliMonitor. The
minimum ratio beteen log. 1 and log. 0 has to be 1:1
This Binary input is not IS-NT archives.