Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
65
Value Description
Dimension
InteliMonitor
IG-NT
IS-NT
SystPfCtrl
System PF control
-
YES
YES
YES
Force value group
ExtValue1-4
ExtValue1 up 1-4
x
YES
YES
YES
Load shedding group
StartLdShed
Start load shedding
-
YES
NO
NO
Hint:
Actual power request is the requested power for the actual gen-set.
*Requested engine speed is transcived value via CAN bus to ECU unit. This value is valid only when ECU
unit is configured
System load control reflects setpoint ProcessControl:
Load ctrl PtM
System PF control reflects the setpoint ProcessControl:
PF ctrl PtM
Statistics
The IGS-NT controller are equipped with statistics values. Statistics values are configurable from
InteliMonitor or GenConfig. They are visible on the controller screens.
kWhours
Is the sum of kWhours produced by the gen-set.
kVArhours
Is the sum of kVArhours produced by the gen-set.
Run hours
Number of total run hours. Run hours are counted in the Control unit only when ECU is not configured or
ECU unit does not send this statistics value. In the case of when the ECU provide Run hours controllers
statistics value Run hours is overdrawed by this value.
Num starts
Is the total sum of gen-set successful starts
NumUnscStarts
Is the total sum of gen-set unsuccessful starts
Service time X
Is the result of Service time X timer. Service Time is decremented and the actual value is visible on the
controller screen
TotalDownTime
Is sum of time when the controller is in OFF mode or any protection of second level is active or not confirmed
DnTimeReqToRun
Is the sum of time when the controller is in OFF mode or any protection of second level is active or not
confirmed and binary input Rem start/stop / Sys start/stop is simultaneously active
PulseCounter
Is the sum of pulses the control unit recognise on configured inputs.
PulseCounter X
Is the sum of pulses the control unit recognise on configured inputs.