Chapter 4 Removing and Replacing FRUs
Replacing Backplane Modules on a Catalyst 4507R or 4510R Switch
4-30
Catalyst 4500 Series Switches Installation Guide
78-14409-08
Verify the New Modules
After the switch is reassembled and power is restored, connect a terminal to the
supervisor engine and monitor the boot process. Look for the following messages
(or any others), which may indicate a problem with the replaced modules:
00:00:20: %C4K_SUPERVISOR-2-MUXBUFFERNOTPRESENT: Mux buffer
(WS-X4K-MUX) 3 is not present
00:00:20: %C4K_SUPERVISOR-2-MUXBUFFERNOTPRESENT: Mux buffer
(WS-X4K-MUX) 4 is not present
00:00:20: %C4K_SUPERVISOR-2-MUXBUFFERNOTPRESENT: Mux buffer
(WS-X4K-MUX) 7 is not present
The above messages (either at startup or output from a
show logging
command)
indicate that the mux-buffer is not present in slots 3, 4 and 7. You need to reinsert
and reseat the modules in those slots.
If the switch has already started up, you may also verify the correct function of
the new modules with the
show logging
command.