CR10X Reference Manual
9-34
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
2
UDG01 SDM address (Base 4)
02:
4
Input location number for air
temperature
03:
4
Input location number for distance
04:
FP
Multiplier
05:
FP
Offset
Input locations altered: 1
Instruction 109: SDMX50 Channel Select
This instruction is used by to manually select probes on the Campbell Scientific
TDR Soil Moisture Measurement System.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
2
SDMX50 Address (Base 4)
02:
2
SDMX50 channel number
Input locations altered: 0
Instruction 110: SDM Group Trigger
This instruction is used to synchronise the measurements of up to 15 SDM
sensors that support the group trigger protocol. The data is retrieved with the
appropriate device-specific instruction. Instruction 110 does not have any
parameters.
Instruction 113: SDM-SIO4
This instruction communicates with the SDM-SIO4 serial input multiplexer. See
the SDM-SIO4 manual for further details.
Instruction 114: Set Time
This instruction can be used to set the CR10X clock from values in input
locations.
PARAM.
DATA
NUMBER
TYPE
DESCRIPTION
01:
2
Option code:
0 set time with hr, min,sec with values using
three input locations
1 set time with day,hr,min,sec using four
input locations
2 set time with yr,day,hr,min,sec using five
input locations
02:
4
Starting Input location number