Appendix I. Modbus on the CR10 and CR10X
I-3
I.3.1 Example 1: Function 1 to Read Coils 1 to 16 from Slave
Device 17
Hex
Slave address
11
Function
01
Starting Address Hi
00
Starting Address Lo
00
No. of Points Hi
00
No. of points Lo
16
Error check (LRC or CRC) --
The coil status is returned as one coil per bit of the data field. Coils 1 to 16 are
addressed as 0 to 15. Response for example 1 follows:
Binary
Hex
8765 4321
Slave address
11
Function 01
Byte Count
02
Data (Coils 7-0)
CD
1100 1101
Data (Coils 15-8)
6B
0110 1011
Error check (LRC or CRC) --
The status of coils 7-0 is CD hex, or 1100 1101 binary. Coil 15 is the Most
Significant Bit (MSB). The CR10’s C1, C3, C4, C7, C8 are on, C2, C5, and C6
are off. Flags 1,2,4,6, and 7 are high.
I.3.2 Example 2: Function 3 to Read Registers 40009 to 40012
from Slave Device 17 to Retrieve Input Locations 5 and 6
from the CR10/10X
Hex
Slave address
x11
Function
03
Starting Address Hi
00
Starting Address Lo
09
No. of Points Hi
00
No. of points Lo
04
Error check (LRC or CRC) --