CR10X User Guide
3-12
Table 3-9 Error Codes
Code
Type
Description
03
Editor
Program Table full
04
Compile
Intermediate Storage full
05
Compile
Storage Area 2 not allocated
08
Run Time
CR10X reset by watchdog timer
09
Run Time
Insufficient Input Storage
10
Run Time
Low battery voltage
11
Editor
Attempt to allocate more Input or Intermediate
Storage than is available
12
Compile
Duplicate *4 ID
20
Compile
SUBROUTINE encountered before END of
previous subroutine
21
Compile
END without IF, LOOP or SUBROUTINE
22
Compile
Missing END (P95)
23
Compile
Non-existent SUBROUTINE
24
Compile
ELSE in SUBROUTINE without IF
25
Compile
ELSE without IF
26
Compile
EXIT LOOP without LOOP
27
Compile
IF CASE without BEGIN CASE
30
Compile
IF and/or LOOP nested too deep
31
Run Time
SUBROUTINES nested too deep
32
Compile
Instruction 3 and interrupt subroutine use same
port
33
Compile
Cannot use Control Port 6 as counter or interrupt
subroutine with Instruction 15 or SDM
40
Editor
Instruction does not exist
41
Editor
Incorrect execution interval
60
Compile
Insufficient Input Storage
61
Compile
Burst Measurement Scan Rate too short
62
Compile
N<2 in FFT
68
Compile
Instruction 118 without enough Instructions 68 or
63
92
Compile
Instruction 92, intervals in seconds: Time into
Interval >59 or Interval >60
94
*D MODE
Program Storage Area full
95
*D MODE
Program does not exist in flash memory
96
*D MODE
Addressed device not connected or wrong address
(see Table 1-8).
97
*D MODE
Data not received within 30 seconds
98
*D MODE
Uncorrectable errors detected
99
*D MODE
Wrong file type or editor error