AFX SERIES® OPERATION MANUAL
SECTION 5: UNPACKING AND INSTALLATION
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 61 of 402
5.13.4
Single Phase Load Output Connection
Connection of a single phase or DC load can be accomplished by using the three phase
mating connector provided in the AFX Series® ship kit. This requires shorting of the three
phases or DC outputs. A power splicer terminal block like the one shown here may be used.
Example of suitable splicer block is Marathon P/N 1322570, 600V, 175A.
Alternatively, the optionally available AFX Single Phase Shorting Adaptor may be used. (Part
number 160086. Not included in AFX Series® ship kit but available through customer
service).
Figure 5-10: Optional AFX Single Phase Shorting Adaptor assembly
Connect phase A+B+C output to the Line connection of the AC load or DC+ side for a DC
load. Connect all three-phase output connections to the Neutral connection of the AC load
or the DC- side for a DC load. Refer to Figure 5-11 for single-phase mode load connection
diagram.