AFX Series Power Source Operation Manual
Page 262 of 402
8.7.8
Power Protection Programming Commands
Command Syntax
[SOURce:]POWer:LIMit#
Description
This command sets the programmable true power limit level in kW
for phase #. If # is omitted, all available phases are set to the value
specified. The max available power for a phase can be obtained using
the [SOURce:]POWer:LIMit#:MAX? query command.
Parameters
Limit value in kW
Parameter Format
<nr2>
Example
POW:LIM 2.5
Query Format
[SOURce:]POWer:LIMit#?
Returned Data Format
<nr2>
Query Example
POW:LIM1?
2.5000
Query Format
[SOURce:]POWer:LIMit#:MAX?
Description
Returns maximum available true power capability for the specified
phase # in kW. If # is omitted, returns maximum available power level
for last phase selected. Typically, this value will be the same for all
phases.
Returned Data Format
<nr2>
Query Example
POW:LIM1:MAX?
5.0000
Command Syntax
[SOURce:]POWer:PROTect:LEVel
Description
This command sets the power protection trip level in kW for all
available phases. If the true power of any phase exceeds this trip
level, the power source will shut off the output to protect the load.
Parameters
True power trip limit level in kW
Parameter Format
<nr2>
Example
POW:PROT:LEV 2.7555
Query Format
[SOURce:]POWer:PROTect:LEVel?
Returned Data Format
<nr2>
Query Example
POW:PROT:LEV?
2.7555