Command Syntax
[SOURce:]INITial <n>
Description
Sets source output settings initialization mode. This command in
combination with the “OUTPut[:STATe]:AUTO” command allows the
unattended resumption of a test station after a power failure.
Note: This condition is potentially hazardous and should be used
with caution.
[SOURce:]INITial? = ON Set points of the unit at power on will be the last set after power off.
The set points affected by this command are:
- Frequency
- Voltage AC1
- Voltage AC2
- Voltage AC3
- Voltage DC1
- Voltage DC2
- Voltage DC3
- Form (THREE , SPLIT or SINGLE)
- Range (High or Low)
- Compatibility Mode (UPC or NORMAL)
[SOURce:]INITial? = OFF Set points of the unit at power on will have a default value of:
- Frequency = 60Hz
- Voltage AC1 = 0V
- Voltage AC2 = 0V
- Voltage AC3 = 0V
- Voltage DC1 = 0V
- Voltage DC2 = 0V
- Voltage DC3 = 0V
- Form = THREE
- Range = HIGH
- Compatibility = NORMAL
Parameters
< 0 | OFF | 1 | ON >
Parameter Format
<b>
Example
:INIT ON
Query Format
[SOURce:]INITial?
Returned Data Format
<b>
Query Example
INIT?
0
Command Syntax
[SOURce:]FORM <nr1>
Description
Set phase mode or FORM. Allowable arguments are 1, 2 or 3.
Parameters
< 1 | 2 | 3 >
Parameter Format
<nr1>
Example
FORM 3
Query Format
[SOURce:]FORM?
Returned Data Format
<nr1>
Query Example
FORM?
3