AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 213 of 402
Command Syntax
OUTPut[:STATe]:AUTO
Description
This commands determines the state of the OUTPUT when the power
source is turned on (powered on).
OUTPut:AUTO = ON The output will be enabled at power on IF it was ON at the time the
front panel circuit breaker of the unit was switched off. Thus, the
output state will revert to the last state before power-off. This
command in combination with the “[SOURce:]INITial” command
allows the unattended resumption of a test station after a power
failure.
Note: This condition is potentially hazardous and should be used with
caution.
OUTPut:AUTO = OFF The output will always come up in the OFF state.
Parameters
< 0 | OFF | 1 | ON >
Parameter Format
<b>
Example
OUTP:AUTO ON
Query Format
OUTPut[:STATe]:AUTO?
Returned Data Format
<b>
Query Example
OUTP:AUTO?
1
Command Syntax
OUTPut:DISABLEPHase
Description
This command sets the disable phase angle. This is the phase angle
on phase A at which the power source output will be disabled.
Available range is 0 ~ 360. Also allows a negative number that
indicates a RANDOM phase angle/
Note: Available in units with Firmware revision 1.6.6 or higher.
Refer also to the OUTPut:ZEROprogram command.
Parameters
0.0 ~ 360.0 or negative number
Parameter Format
<nr2>
Example
OUTPDISABLEPH 90.0
OUTPDISABLEPH -1
Query Format
OUTPut:DISABLEPHase?
Returned Data Format
<nr2>
Query Example
OUTP:DISABLEPH?
90.000