Error Source
Code
Category
Error Message
Possible Cause
Resolution
Front panel
Fault
361
Error
Did not receive MDO 1 -
Inverter C.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
Fault
362
Error
Did not receive MDO 2 -
Inverter C.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
Fault
363
Error
Did not receive MDO 3 -
Inverter C.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
Fault
364
Error
Did not receive MDO 4 -
Inverter C.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
Front panel
Fault
365
Error
Did not receive MDO 5 -
Inverter C.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
I/O Board
Fault
394
Error
Internal board fault.
Hardware Fault
Try recycling power. If
error persists, contact
customer service
I/O Board
Fault
395
Error
Invalid node ID. Run unit
discovery to recover.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cable connections
if present and then turn
unit back on. If problem
recurs, contact customer
service.
I/O Board
Fault
396
Error
Incorrect DSP type
detected. Cycle-power to
re-try.
Internal Communication
Error. AUX I/O processor
not responding
Try recycling power. If
error persists, contact
customer service
I/O Board
Fault
397
Error
Invalid constants loaded
from EEPROM.
Configuration Error.
Coefficients found are
invalid.
Sanitize unit to restore
factory defaults