AFX SERIES® OPERATION MANUAL
SECTION 13:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 385 of 402
Error Source
Code
Category
Error Message
Possible Cause
Resolution
Front panel
Error
190
Error
Master unit nodes not
found.
Error during discovery.
One or more nodes in
Master unit not found
Turn unit off, check
parallel cables if they
exist, and then turn unit
on. If problem recurs
contact customer service.
Front panel
Error
191
Error
Fast scan failed.
Error during discovery.
Fast scan discovery failed
Check all parallel cables
between units. Run
parallel unit discovery
from System menu to
recover
Front panel
Error
192
Error
Undetectable node exists.
An inconsistency was
detected in the power
source's internal
communication network.
Turn unit off, check
parallel cables if they
exist, and then turn unit
on. If problem recurs
contact customer service.
Front panel
Error
193
Error
An invalid firmware type
exists.
Firmware Error. One or
more nodes report invalid
firmware type
Check for correct
firmware image file and
version.
Primary Fault
200
Error
LLC primary/auxiliary
current peak limit
exceeded.
Primary Fault
201
Error
LLC/PFC gate driver fault
or hardware OVP.
Primary Fault
202
Error
Controller missed
heartbeats from master
front panel.
Primary Fault
203
Error
LLC primary current
average limit exceeded.
Primary Fault
204
Error
LLC auxiliary current
average limit exceeded.
Primary Fault
205
Error
PFC current peak limit
exceeded.
Primary Fault
206
Error
PFC DC bus voltage limit
exceeded.
Primary Fault
207
Error
Gate driver fault
Gate driver fault occurred
in Input Buck Converter.
Check for correct AC
input voltage connection.
Primary Fault
208
Error
Input buck switching
time.
Primary Fault
209
Error
AC input current
exceeded RMS limit for
too long.
Primary Fault
210
Error
Unbalanced current in
PFC boost converters.
Primary Fault
211
Error
PFC efficiency protection.
Primary Fault
212
Error
AC input: voltage is below
minimum.
Primary Fault
213
Error
AC input: missing phase.
Primary Fault
214
Error
PFC DC bus voltage
regulation lost.
Primary Fault
215
Error
PFC DC bus voltage limit
exceeded. CLA OVP Trip