113/240
the filter table.
19.5.3.2
KNX --> IP Group telegrams
main group 14+15
(Tab
Basis
)
Via the
KNX --> IP Group telegrams main group 14+15
,
the transfer of group telegrams with main group addresses
14 and 15 from the Sub line to the Main/area line is blo-
cked or enabled. When selecting
Filter
only telegrams with
main group addresses 14 and 15 that are listed in the filter
table are transferred.
19.5.3.3
IP --> KNX Group telegrams
main group 0-13
(Tab
Basis
)
Via the parameter
IP --> KNX Group telegrams main
group 0-13
is used to block or enable the transfer of group
telegrams from the Main/area line to the sub line. When
selecting
Filter
only telegrams that are listed in the filter
table are transferred.
19.5.3.4
KNX --> IP Group telegrams
main group 0-13
(Tab
Basis
)
The parameter
KNX --> IP Group telegrams main group
0-13
blocks or enables the transfer of group telegrams with
main group addresses 0 and 13 from the Sub line to the
Main/area line. When selecting
Filter
only telegrams with
main group addresses 0 and 13 that are listed in the filter
table are transferred.
19.5.3.5
IP --> KNX Physically
addressed telegrams
(Tab
Physical address
)
The
IP --> KNX Physically addressed telegrams
parameter
is used to set the transfer of physically addressed telegrams
from the main/area line to the sub line (e.g. programming
an application or for diagnostics purposes during the en-
quiry of the device state).
Filter
,
Block
and
Transfer
can be
set.
With the
Transfer
setting, the IP router only transfers tele-
grams with a physical address as target address if they
match the subordinate side (TP or PN connection of the IP
router). The IP router's own physical forms the basis for
the synchronisation.
Summary of Contents for Busch-ComfortTouch
Page 1: ...Product manual Busch ComfortTouch Busch ComfortTouch www BUSCH JAEGER de ...
Page 16: ...16 240 ...
Page 147: ...147 240 03_03_09_00_EN html Logikbausteine ...
Page 155: ...155 240 03_03_09_00_EN html Logikbausteine 03_03_09_00_EN html Boolean ...
Page 217: ...217 240 03_03_09_00_EN html weitere_math 03_03_09_00_EN html weitere_math ...
Page 226: ...226 240 03_03_09_00_EN html Signalkontrolle ...