233/240
20.3.46
Demultiplexer details
20.3.46.1
Behaviour
If this module receives a value via the
Input 0
, it on one of up to eight outputs (
Outputs 0
to
7
.
The value of the
Input 1
specifies which output is to be selected. If an invalid value is received
on
Input 1
, no new output is selected.
The data type of the
Input 1
is Number. If necessary, incoming values are converted before the
calculation (see conversion table below).
20.3.46.2
Extended settings
Via the
Smallest Index
parameter, you can specify whether the numbering of
the outputs should start with 0 or with 1.
Via the
Number of outputs
parameter, you can specify how many outputs shall
be available.
Via the
Only send with change
parameter, you can specify whether an output
value shall only be sent if the current input value is different from the previously
received input value.
20.3.46.3
Conversion table
Number
(converted)
Boolean
true
false
→
→
1
0
Number ---
DPTTime
Milliseconds
since 1.1.1970
DPTDate Number