235/240
20.3.47
Multiplexer details
20.3.47.1
Behaviour
If this module receives a value via one of the up to eight inputs (
Input 0
to
7
), it outputs this
value on the
Output 0
. The value of the
Input 8
specifies which input is to react to incoming
values. If an invalid value is received on
Input 8
, no new input is selected. Once a new input is
selected, the last received value there is output on
Output 0
.
The data type of the
Input 8
is Number. If necessary, incoming values are converted before the
calculation (see conversion table below).
20.3.47.2
Extended settings
Via the
Smallest Index
parameter, you can specify whether the numbering of
the outputs should start with 0 or with 1.
Via the
Number of inputs
parameter, you can specify how many inputs shall be
available.
Via the
Only send with change
parameter, you can specify whether an output
value shall only be sent if the current input value is different from the previously
received input value.
20.3.47.3
Conversion table
Number
(converted)
Boolean
true
false
→
→
1
0
Number ---
DPTTime Milliseconds