53-1004106-15 Installation Guide
Brocade
®
X6-4 Director Hardware Installation Guide
5. Verify firmware installation by following all steps under
.
6. Verify operation of the replacement blade by following the steps under
7. Repeat the preceding steps to replace the other CP blade if necessary.
Replacing a CP Blade (Cold-Swap)
Use this procedure to replace CP blades after removing power to the device.
1. Prepare for replacing the blade by following all steps under
2. Remove the blade following all steps under
3. Install the blade following all steps under
4. Verify firmware installation by following all steps under
.
5. Verify operation of the replacement blade by following the steps under
Time and Items Required
The replacement procedure for the CP blade takes approximately 30 minutes. The following items are required for the CP
blade replacement:
•
Electrostatic discharge (ESD) grounding strap
•
Workstation computer
•
Serial cable
•
IP address of an FTP server for backing up the device configuration
•
No. 1 Phillips screwdriver
•
Replacement CP blade
Preparing for Replacement
Use this procedure to prepare the system for CP blade replacement.
1. Back up the device configuration before you replace a CP blade by uploading various device configuration files using a
Telnet connection and saving them to a host computer. Before you upload a configuration file, verify that you can reach
the FTP server from the device.
Perform the following steps:
a) Enter the
configupload -all
command, specifying a file name for saving configuration data.
This saves all system configuration data including chassis and switch configuration for all logical switches to the file
name specified. For more information, refer to the
Brocade Fabric OS Command Reference Manual
.
b) Enter the
configupload -vf
command, specifying a file name, when prompted, for saving configuration data.
This saves the backbone virtual fabric data to the file name specified. For more information, refer to the
Brocade
Fabric OS Command Reference Manual
.
c) In a FICON environment, log on as root and enter
configupload --map
to upload port-to-area mapping
information. Specify a folder name, when prompted.
This command saves the port-to-area addressing mode configuration files to the folder specified. Be sure to upload
the configuration using the
-map
option for a FICON-enabled device if port-bound addressing is used. For more
information, refer to the
Brocade Fabric OS Command Reference Manual
.
2. Connect to the device and log on as
admin
using a serial console connection.
3. Enter
haShow
to determine which CP blade is active.
Gen7-4:admin> hashow
Local CP (Slot 1, CP0): Active, Warm Recovered
Remote CP (Slot 2, CP1): Standby, Healthy
53-1004106-15
126