T200 IDSL OFFICE CHANNEL UNIT - REMOTE (IDSL OCU-R)

INSTALLATION & TURNUP

1. Select desired options with front panel DIP switches SW1 and SW4.
2. Insert the IDSL OCU-R into its designated slot ensuring the edge connector seats firmly into the

backplane.

3. After insertion the IDSL OCU-R will run a self-test and synchronization phase during which all LEDs

undergo an On/Off sequence.  Refer to 

Status LEDs

section for descriptions.

4. After synchronization, which may take up to 50 seconds, the following LED indication will show:

SYNC LED - Green.

All other LEDs will be Off until network occurrences cause them to turn On.

If LEDs in step 4 are as noted, proceed with loop testing per specifications.
If LEDs in step 4 are in any other configuration, refer to 

Troubleshooting Guide 

section.

CAUTION:

This product is intended for installation

in a restricted access location in a Type “B” or “E”
enclosure only.

Max input current @ max load = 32 mA @ -48 VDC
with an output of 6 mA @ 10 VDC.

WIRING CONNECTIONS

HARDWARE VERSUS SOFTWARE PROVISIONING

When SW1 and SW4 are used for option selection the options take effect when the card is inserted in the
mounting.  Subsequent software provisioning will override hardware options.  Depressing the LBK
pushbutton for five seconds will toggle between the two option sets.

INSERTION LOSS MEASUREMENTS

IDSL Design Limits at Traditional 4-Wire
Frequencies.

TYPICAL APPLICATION

JOB

A

ID

61220010L2-22C

0111

IDSL OCU-R  

CLEI: NCT1TX2B_ _

T-Carrier

Channel Bank

2-Wire Loop

4-Wire Customer

Interface

T/R Pair

Customer Premises

U-BR1TE

IDSL

OCU-R

DSU/CSU

Customer

4-Wire Qualifying

IDSL Loss

Rate

Frequency (kHz)

Limit (dB)

2.4

1.2

14

2.4/SC

1.6

14.5

4.8

2.4

16

4.8/SC

3.2

17

9.6

4.8

19

9.6/SC

6.4

20.5

19.2

9.6

24

19.2/SC

12.8

27

56

28.0

35

56/SC & 64

36.0

36

STATUS LEDs

SYNC

GREEN

Loop synchronized.

RED

Loop not synchronized.

CRC

ON

Errors on 2-wire loop.

NO DSU

ON

Customer DSU/CSU not responding/installed.

AP

ON

Remotely provisioned option set in effect.

FLASHING Remote control link active.

OFF

DIP switch option set in effect.

NTWK LBK

ON

OCU loopback toward network exists.

FLASHING Channel loopback at CSU exists.

CUST LBK

ON

IDSL OCU-R in loopback toward customer. 

FLASHING Loopback toward the customer at the ADTRAN U-BR1TE.

NOTE:

All LEDs OFF indicates loss of power or other malfunction.

FRONT PANEL OPTION FEATURES

FRONT PANEL LBK PUSHBUTTON SW2

Loopback pushbutton SW2 initiates loopback tests without CO or test center coordination.
Refer to LBK Pushbutton in 

Testing

section.  Depressing the LBK pushbutton for five seconds

will toggle between hardware and software option settings.  The AP LED provides indication.

FRONT PANEL DIP SWITCH SW4

SC

ON

Enables secondary channel when 56k or below data rate is selected.

64

ON

Selects 64 kbps data rate (SC must be set to OFF).

56

ON

Selects 56 kbps data rate.

19.2

ON

Selects 19.2 kbps data rate.

9.6

ON

Selects 9.6 kbps data rate.

4.8

ON

Selects 4.8 kbps data rate.

2.4

ON

Selects 2.4 kbps data rate.

SW56 ON

Selects switched 56 data rate (SC must be set to OFF).

FRONT PANEL DIP SWITCH SW1

-10 dB ON

Selects -10 dB AMI signal across 4-wire interface to customer. (Typical installation)

OFF Selects 0 dB AMI signal across 4-wire interface to customer. (Extended demarcation

installation)

QM

ON

Enables Quality Monitoring.  Excessive errors will cause automatic blockage of data.

OFF Quality Monitoring disabled.

EC

ON

Enables Error Correction, valid only at 19.2 kbps or lower.

OFF Error Correction disabled.

LLEN ON

Enables response to latching loopbacks.

OFF Disables response to latching loopbacks.

FRONT PANEL DB-9 CONNECTOR

Provides an RS-232 interface for connection to a VT100 or compatible terminal or test device.

COMPATIBLE HOUSINGS

Any standard T400/T200 housing, or these ADTRAN housings:

Span Power Applications

Single mount housing, P/N 1212007L1

Dual mount housing,

P/N 1212008L1

Local Power Applications

Single mount housing, P/N 1212007L2

DEPLOYMENT GUIDELINES

All loops must be non-loaded.

Actual Measured Loss not to exceed 40 dB at 40 kHz, 135 

termination, the Nyquist 

frequency of IDSL.

Recommended bridged tap length should not exceed 2 kft.

■ 

For a complete Installation and Maintenance Practice faxback: (877) 457-5007, Document #574.  Please have your fax number available. 

■ 

Pair

Terminal Strip Designations

T400 PIN Number

Customer RJ-48

To/From Network

TT, TR

41, 47

To Customer

DRT, DRR

5, 15

7, 8

From Customer

DTR, DTT

49, 55

1, 2

Frame Ground

GND

11, 27

Local -48 Vdc

GND

17

Local -48 Vdc

PWR

35

Code

Input

Output

Power Code (PC)

F

C

Telecommunication Code (TC)

X

Installation code (IC)

A

CAUTION:

On span-powered units, ensure ground

continuity exists between the unit, the housing,
and a known approved ground source.

C A U T I O N 

C A U T I O N ! 

SUBJECT TO ELECTROSTATIC DAMAGE

OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.