53-1004106-15 Installation Guide
Brocade
®
X6-4 Director Hardware Installation Guide
Power Supply Specifications (Per PSU)
Power Supply Model
Maximum
Output Power
Rating (DC)
Output Power
vs. Input Voltage
Input Line
Frequency
Maximum
Input
Current
Input Line
Protection
Maximum
Inrush Current
AC power supply
FRU numbers:
XBR-X6-RACNPIPSU-0104
XBR-X6-RACNPEPSU-0104
1450W/2870W
1450W Output
100–120 VAC
(nominal)
90–132 VAC (range)
2870W Output
200–240 VAC
(nominal)
180–264 VAC (range)
50–60 Hz
(nominal)
16A
Line &
neutral
fused
35A peak for
< 10 ms at cold or
warm start.
25A peak for cycles
10 ms to 150 ms.
Less than fuse rating
for > 150 ms.
HVAC/HVDC power supply
FRU numbers:
XBR-X6-HVNPIPSU-0104
XBR-X6-HVNPEPSU-0104
2870W
180–305 VAC (range)
2870W Output
240–380 VDC
(nominal)
192–400 VDC (range)
50–60 Hz
(nominal)
16A
Line &
neutral
fused
35A peak for < 10 ms
at cold or warm start.
25A peak for cycles
10 ms to 150 ms.
Less than fuse rating
for > 150 ms.
Power Supply Requirements
The minimum number of power supplies needed in your system for operation and to achieve redundancy depends on the
blade and port configuration and on the AC or DC input voltage level:
•
N is the minimum number of power supplies to operate the configuration.
•
N+N doubles the number of power supplies for full AC or DC input and DC output redundancy
•
N+1 adds an additional power supply for DC output redundancy in the case of a single power supply failure.
Although examples for different port and blade configurations are provided, for more information and help with determining
the actual number of power supplies for your deployment, contact your local Brocade representative.
NOTE
In the following table, HVAC and HVDC indicate voltages from the high-voltage AC and high-voltage DC power
supply.
Model Name
Configured Ports
Input Connection
Minimum Power
Supplies for
Operation
Number of Power
Supplies for
Redundancy
100–120 VAC (low line)
2
Not supported
Brocade X6-4
Any combination of 32G
ports, Extension blades,
and QSFP ICLs
200–240 VAC (high line)
200–277 HVAC (high line)
240–380 HVDC
1
2 (N+N)
Fibre Channel Data Transmission Ranges
Port Speed (G)
Cable Size
(Microns)
Short Wavelength (SWL)
Long Wavelength (LWL)
Extended Long
Wavelength (ELWL)
50
150m (492 ft) (OM2)
380m (1264 ft) (OM3)
400m (1312 ft) (OM4)
N/A
N/A
4
62.5
70m (229 ft)
N/A
N/A
53-1004106-15
188